SIMPLEX 4100 FIRE INDICATOR PANEL Page 7
OPERATOR MANUAL
Document No: 4100-M001 May 1997 Issue 1.0
A. Unlock and open the panel door. The Fire Alarm Bell will now stop
sounding due to the panel door being opened. However the ISOLate LED will
be flashing due to the fact that the door has been opened. Read the
alphanumeric display. It shows the number of alarm conditions.
***ALARM*** Press <ACK> to review.
ALARMS = 1 ISOLATED = 0 FAULT = 0
B. Press the <ALARM ACK> key. Read the alphanumeric display.
- The tone-alert is silenced and the display will show pertinent report
information, such as shown below.
1st Floor East Wing Room 2 AZF1
SMOKE DETECTOR ALARM
C. Press the <SUPV ACK> key.
- System Isolate LED will stop flashing and the tone -alert will be silenced to
indicate that the panel door has been opened and the Alarm Bell is isolated.
When the alarm condition has been cleared, restore or replace all affected
devices (MCPs, smoke detectors etc.) in accordance with the instructions
provided with each device.
After a delay, the system should show the following:
SIMPLEX AUSTRALIA SYSTEM IS NORMAL
8:23:43 MON 25 JAN 95
3.2 ESSENTIAL ALARM CONDITION KEYS
The essential keys for alarm conditions are the <ALARM ACK>, The remaining
keys are concealed by the access door and are associated with advanced
functions of the system (See Advanced Functions Section 5.)
3.2.1 Alarm Ack (acknowledge)
The <ALARM ACK> key is located directly under the system alarm LED. Pressing
the <ALARM ACK> key will cause the LED to change from flashing to a steady ON
condition and silence the tone-alert.