Installation manual

SIMPLEX 4100 FIRE INDICATOR PANEL Page 43
OPERATOR MANUAL
Document No: 4100-M001 May 1997 Issue 1.0
7.8.11 System Fault
The Walk Test has the ability to test signal circuits for fault (i.e. open/short)
conditions. This is accomplished by using the Walk Test output lists (L50 through
L57) as the input lists for signal fault conditions.
For example, if a signal circuit fault occurs on a point in Walk Test output list L50
(Group 0), and Walk Test Group 0 is enabled, the Walk Test fault code will play
on all signal/speaker circuits in Walk Test list L50. Note that the signal fault is not
inhibited. An actual fault condition will occur at the operator interface panel, but will
be logged as a Walk Test fault for that signal. This fault automatically clears when
the signal circuit is returned to normal in a Global Acknowledge system. In an
Individual Acknowledge system, Point P4 (FORCE GLOBAL ACKNOWLEDGE)
must be turned ON before performing a signal circuit Walk Test. If Walk Test is
not enabled for the group containing the signal circuit in fault, the fault condition
passes through without playing the Walk Test code.
7.8.12 Fault Audible
When a zone fault is detected, the Walk Test signals sound continuously for four
seconds.
7.8.13 Zone Code/Zero Code
The <F3> key is used to enable/disable Zone Coding. By default, Zone Coding is
enabled.
7.9 Walk Test PROCEDURES
Before the Walk Test can be performed, the operator must enter the correct
passcode.
7.9.1 How to Enter a Walk Test Passcode
To enter the passcode, perform the following procedures.
1. Open the access door; then, press the <MENU> key. The LCD displays the
following message.
Press <NEXT> or <PREVIOUS> to Scroll
Change Access Level?