Specifications

I.B. ATS-I005
Page 10
Effective 6/00
Table 2.1 IQ Transfer Specifications
Parameter Specification
Figure 2-3 Communication Module - PONI (mounted)
Control Power: 120Vac (50/60 Hz) (operating range 65 to 160 Vac)
Power Consumption: 18VA
Environmental Conditions:
Operating Temperature
-20° to 70°C
Operating Humidity
up to 90% Relative Humidity (non-condensing)
Enclosure Compatibility: NEMA 12 (standard mounting)
NEMA 4/4X (mounted with gasket between panel and device faceplate)
NEMA 3R (outdoor)
UV Resistant IQ Transfer Faceplate
System Voltage Application: 120 to 600 Vac (50/60 Hz) (single or three phase)
Voltage Measurements: Source 1, Source 2 and Load (VAB, VBC, VCA for Three Phase System)
Voltage Measurement Range: 0 to 700 Vac
Voltage Measurement Accuracy: ±1% of Full Scale
Frequency Measurements: Source 1 and Source 2
Frequency Measurement Range: 40 to 80 Hz
Frequency Measurement Accuracy: ±0.1 Hz
Undervoltage Dropout Range: 50 to 97% of Nominal System Voltage
Overvoltage Dropout Range: 105 to 120% of Nominal System Voltage
Underfrequency Dropout Range: 90 to 97% of Nominal System Frequency
Overfrequency Dropout Range: 103 to 110% of Nominal System Frequency
Applicable Testing: UL Recognized Component
Meets Seismic Requirements of Uniform and California Building Codes
(exceeding requirements of worst case Zone 4 levels)
Meets Intent of UL991
Meets IEC 801-2, 3, 4 and 5
Meets CISPR 11
Complies with FCC Part 15, Subpart B, Class A