Specifications
I.B. ATS-I005
Page 10
Effective 6/00
Table 2.1 IQ Transfer Specifications
Parameter Specification
Figure 2-3 Communication Module - PONI (mounted)
Control Power: • 120Vac (50/60 Hz) (operating range 65 to 160 Vac)
Power Consumption: • 18VA
Environmental Conditions:
Operating Temperature
• -20° to 70°C
Operating Humidity
• up to 90% Relative Humidity (non-condensing)
Enclosure Compatibility: • NEMA 12 (standard mounting)
• NEMA 4/4X (mounted with gasket between panel and device faceplate)
• NEMA 3R (outdoor)
• UV Resistant IQ Transfer Faceplate
System Voltage Application: • 120 to 600 Vac (50/60 Hz) (single or three phase)
Voltage Measurements: • Source 1, Source 2 and Load (VAB, VBC, VCA for Three Phase System)
Voltage Measurement Range: • 0 to 700 Vac
Voltage Measurement Accuracy: • ±1% of Full Scale
Frequency Measurements: • Source 1 and Source 2
Frequency Measurement Range: • 40 to 80 Hz
Frequency Measurement Accuracy: • ±0.1 Hz
Undervoltage Dropout Range: • 50 to 97% of Nominal System Voltage
Overvoltage Dropout Range: • 105 to 120% of Nominal System Voltage
Underfrequency Dropout Range: • 90 to 97% of Nominal System Frequency
Overfrequency Dropout Range: • 103 to 110% of Nominal System Frequency
Applicable Testing: • UL Recognized Component
• Meets Seismic Requirements of Uniform and California Building Codes
(exceeding requirements of worst case Zone 4 levels)
• Meets Intent of UL991
• Meets IEC 801-2, 3, 4 and 5
• Meets CISPR 11
• Complies with FCC Part 15, Subpart B, Class A