Specifications

I.B. ATS-I005
Page 22
Effective 6/00
SECTION 5: PROGRAMMING
5.1 INTRODUCTION
Although all IQ Transfer programmable features are
addressed in this section, only those ordered by the
customer and initially programmed at the factory
will appear in the display for programming changes
in the field.
The IQ Transfer is fully programmable from the device’s
faceplate or through the communications port. Users
can reprogram setpoints as well as other parameters.
The time and date can be changed while the device is in
either the Run Mode or the Program Mode. Setpoints,
however, can only be changed while the device is in the
Program Mode.
5.2 ENTERING AND EXITING THE PROGRAM MODE
While in the Program Mode, IQ Transfer is never off-
line and continues to function in accordance with
previously programmed setpoints.
If no pushbutton activity is detected for approxi-
mately 2 1/2 minutes while in the Program Mode, the
Setpoints LED is cleared and the alpha-numeric dis-
play is blanked. Any previously made setpoint
changes are not saved, should this occur.
When the toggle switch is in the Program position,
remote communications programming is inhibited.
To enter the Program Mode, move the Run/Program
Toggle Switch located on the right rear chassis to the
Program position. Once the Program Mode is activated,
the Program LED blinks red and continues until the
Program Mode is exited.
When programming changes have been completed, the
Program Mode is exited by moving the Run/Program
Toggle Switch back to the Run position. At that point,
the Automatic LED continues to blink green, the
alphanumeric display shows the word “Program” for a
short period, and the Program LED will no longer be illu-
minated. It is also at that point when any setpoint
changes are saved in the device’s non-volatile memory.
5.3 PROGRAMMING PROCEDURES
Once the Program Mode has been entered, use the
Display Select Pushbutton to move to the Setpoints
Display. The Setpoints LED will be lit red and the first
programming possibility will appear in the display. Use
the Step Pushbutton to move from one feature setpoint
to another, stopping at those in need of reprogramming.
Use the Increase or Decrease Pushbuttons to move the
display to a new setpoint selection. Once a new setpoint
selection has been made, move to the next feature in
need of change. Once all setpoints are displayed as
required, exit the Program Mode and the new setpoints
are automatically stored.
5.4 PROGRAMMABLE FEATURES/SETPOINTS
CHANGING THE SYSTEM NOMINAL VOLTAGE OR
FREQUENCY SETPOINTS WILL AUTOMATICALLY
CHANGE ALL THE PICKUP AND DROPOUT SET-
TINGS TO NEW DEFAULT VALUES.
All IQ Transfer programmable features and associated
setpoint possibilities with any required explanations are
presented in Table 5.1. Remember, only features origi-
nally ordered and factory programmed will appear in the
display.
!
CAUTION
NOTICE
NOTICE
NOTICE
NOTICE