Specifications

I31
GE Limitamp
®
Medium Voltage Motor Control
Typical Elementary Diagrams
I
(A2)
(
A1)
(1)
(2)
(2)
(1)
(1P4)(1P3)
(D16)
(D20)
(D19)
(D18)
(D17)
(D21)
(D22)
(D23)
(D24)
GROUND
(G12)
(D11)
(D12)
(D13)
(D15)
(D14)
(D6)
(D7)
(D8)
(D10)
(D9)
(A14)
(A15)
(A13)
(A12)
(A11)
(D4)
(D5)
(D3)
(D2)
(D1)
(A6)
(A7)
(A8)
(A10)
(
A9)
(
F8)(E9)
(B1)
(
F1)(E1)
(C4)
(C3)
(C2)
(C1)
(D27)
(D26)
(D25)
(B4)
(B3)
(B2)
(G11)
(H11)(H12)
(F12)
(E12)
(A18)
(A19)
(
A17)
(
A16)
(A22)
(
A23)
(A21)
(A20)
(A26)
(
A27)
(
A25)
(
A24)
(A1)
(A2)
(A3)
(A5)
(
A4)
(
E7)(F7)
(1P6)(1P5)
5
5
2
2
0
34
D23 D16
17
17
27
27
27
98
MX
1PB
START
2
PB
STOP
M
MULTILIN
GE POWER MANAGEMENT
TECHNICAL SUPPORT
TEL: (905) 294-6222
FAX: (905) 201-2098
469-B1
1
R
T
D
R
T
D
R
T
D
R
T
D
R
T
D
R
T
D
R
T
D
R
T
D
R
T
D
R
T
D
R
T
D
R
T
D
2
3
4
7
8
5
6
9
10
11
12
R6R1
S
ERVICETRIP
SR469
BLOCK
R5
LINK
M
GND GND GND
NOTE: SR469 TO BE PROGRAMED IN FIELD BY OTHERS.
___ OHMS
MATERIAL ___________
RTD 1 - 6 MOTOR STATOR
RTD 7 - 8 MOTOR BEARING
RTD 9 - 10 PUMP BEARING
R
TD 11 PUMP CASE
RTD 12 AMBIENT
C. USE 3 CONDUCTOR SHIELDED CABLE BETWEEN
MOTOR AND MULTILIN SR469 RELAY.
B. RTD SHIELDED CABLE SHIELDS ARE TO BE
GROUNDED AT THE SR469 MOTOR MANAGEMENT
RELAY ONLY. DO NOT GROUND SHIELDS AT MOTOR.
A. DO NOT GROUND ANY RTD LEADS AT MOTOR.
IF ANY GROUND EXISTS AT MOTOR. IT MUST
BE LIFTED.
NOTE INSTALLER
99
(continued on next page)
800A Drawout FVNR with M469 Relay
(Stationary also available)