Specifications
G1
GE Limitamp
®
Medium Voltage Motor Control
Components
G
Components
Typical push buttons, selector switches and control wiring
used in standard Limitamp appear below, and the following
pages detail a range of typical components.
Typical push buttons
Typical selector switches
Control wiring details
Item Standard Option
Control wiring type MTW, thermoplastic, 600V, 90°C SIS (vulkene)
Control wire size AWG #14 AWG #12
Control wire terminals Stripped wire Insulated ring type
Wiremarkers Plastic sleeve type Heat-shrinkable labels
Wire color code
Power-Black
Control-Red
Neutral-White
Ground-Green
Terminal blocks CR151B, 30A, 600V
EB-25, 50A, 600V,
Connectron Type KUX
Function Application Device used
On-Off
Permissive start with 2-,
3-wire control
CR104P maintained type
Hand-Off-Auto
Auto or manual start with
2-wire control
CR104P maintained type
Fast-Slow-Off-Auto 2-speed starters CR104P momentary type
Function Application Device used
Start-Stop
FVNR starters with 3-wire
control
CR104P momentary type
Stop
Starters with 3-wire control
Starters with 2-, 3-wire
control
CR104P momentary type
CR104P maintained type
Options:
Mushroom head
Provisions for locking open
Forward-Reverse-Stop FVR starters CR104P momentary type
Fast-Slow-Stop 2-speed starters CR104P momentary type