Specifications

G11
GE Limitamp
®
Medium Voltage Motor Control
Components
G
Applications
Primary protection for distribution feeders
Stand-alone or component in automated substation
control system
Interlocking scheme on distribution level by means of
Remote I/O features
Throw over schemes (bus transfer scheme)
Load shedding scheme based on frequency elements
Key Benefits
Unparalleled security/safety – downed conductor detection
Reliable Distributed Generation interconnection protection
Dependable and secure – performance backed up by
many years of field experience
Cost effective and flexible access to information – multiple
communication options and protocols
Breaker monitoring – monitor breaker conditioning
through analog I/O, rich metering, breaking arcing current,
and trip counters
Use high speed communications to reduce wiring and
installation costs – exchange inputs and outputs between
relays to achieve relay-to-relay interaction
Reduce installation space requirements through compact
design – multifunction device that integrates protection
and control functions, programmable pushbuttons and
status LEDS, and communication interfaces
Maintenance cost savings and simplification – modular
construction, common hardware, reduced stock of spare
parts, plug & play modules
Application flexibility – multiple I/O options, programmable
logic (FlexLogic
), modularity, customize to specific
requirements
Reduce system event analyzing time and cost – sequence
of event reports, oscillography, datalogging, IRIG-B time
synchronization
Embedded IEC 61850 Protocol – no external protocol
converter required
Features
Protection and Control
Downed conductor detection – high impedance faults
Phase, neutral, ground or sensitive ground and negative
sequence IOCs and TOCs with directional control
Sensitive directional power
Breaker failure
Breaker control
Four-shot autorecloser with synchronism check
Up to 80 digital input and 56 digital outputs
Transducer I/Os (RTD, dcmA)
Wattmetric zero-sequence directional function
Communications
Networking options – Ethernet-fiber (optional redundancy),
RS485, RS422, G.703, C37.94
Multiple protocols – IEC 61850, DNP 3.0 Level 2, Modbus RTU,
Modbus TCP/IP, IEC 60870-5-104, Ethernet Global Data (EGD)
Direct exchange of Inputs/Outputs – exchange of binary
data between URs
Monitoring and Metering
Metering – current, voltage, power, energy, frequency,
voltage and current harmonics, demand (current, power)
Oscillography – 64 samples/cycle, up to 64 records
Event Recorder – 1024 time tagged events, with 0.5ms
scan of digital inputs
DataLogger – up to 16 channels with user selectable
sampling rate
Fault Locator
User Interfaces and Programming
Fr
ont panel display and keypad for local direct access,
with an RS232 port for local PC access
User programmable local display, LEDs and pushbuttons
Customize protection and control functions with
FlexLogic
FlexCurves
, and FlexElements
Includes EnerVista LaunchPad - Simple relay setup and
programming
Multi-language support – French, Chinese, Russian option
Order must include complete catalog number of required
device
F60 Feeder Protection System