Specifications

G14
GE Limitamp
®
Medium Voltage Motor Control
Components
G
Description
The Model LPVRB-120 is designed to protect 3-phase loads
from damaging power conditions. Its wide operating range
combined with UL and CE compliance enables quick access to
domestic and global markets. A unique microcontroller-based
voltage and phase sensing circuit constantly monitors the
three phase voltages to detect harmful power line conditions.
When a harmful condition is detected, the LPVRB-120’s output
relay is deactivated after a specified trip delay. The output
relay reactivates after power line conditions return to an
acceptable level for a specified amount of time (Restart
Delay) or after a manual reset. The trip and restart delays
prevent nuisance tripping due to rapidly fluctuating power
line conditions. An adjustment is provided to set the nominal
line voltage from 95-120 VAC. Other adjustments include a
1-30 second trip delay, a 1-500 second restart delay, and a
2-8% voltage unbalance trip point adjustment. Two LEDs
indicate the status of the Model LPVRB-120; Run Light,
Under Voltage, Over Voltage, Phasing Fault/ Reverse Phase,
and Manual Reset. The LPVRB-120 ships with a jumper
installed for automatic restart. A connector with two 12"
wires is included for manual reset switch.
Key Benefits
Protects 3-Phase motors from:
Loss of any Phase
Low Voltage
High Voltage
Voltage Unbalance
Phase Reversal
Rapid Cycling
Features
Four adjustment pots provide versatility for all kinds of
applications
Range from 95-120 VAC 50/60 Hz provides the versatility
needed to handle global applications
Diagnostic LEDs indicate trip status and provide simple
troubleshooting
Microcontroller based circuitry provides better accuracy
and higher reliability than analog designs
Transient protected to meet IEEE and IEC standards and
operate under tough conditions
Will detect single phase condition regardless of regenerated
voltages
Compact design
UL and cUL listed
CE compliant
Finger safe terminals
• 5 year warranty
Made in USA
Standard surface or DIN rail mount
• Standard 1-500 sec. variable restart delay
• Standard 2-8% variable voltage unbalance
• Standard 1-30 sec. variable trip delay
One 10 amp general purpose Form C relay
Optional manual reset
LPVRB-120 Phase Voltage Relay