Specifications

G24
GE Limitamp
®
Medium Voltage Motor Control
Components
G
Application
Type HWT equipments are suitable for use on indoor or outdoor
primary circuits where small amounts of kVAR are required.
They may be installed at load centers or directly at the
terminals of 2300 and 4000 volt motors. Permissible ambient
temperatures are –40° to +45°C. Discharge resistors in each
capacitor reduce the voltage to 50 volts or less within 5 min-
utes of de-energization. Type HWT equipments contain less
than three gallons of flammable liquid in a single container
and therefore do not require installation in a vault to meet
the NEC.
Specifications
Enclosed Indoor Dustproof and Outdoor Weatherproof
25-900 kVAR, 60 Hz
2400, 4160, 4800 Volts
1.0-200 kVAR, 240 Volt
Line Terminals
Solderless connectors are provided on each phase:
Assembly Connector Size
One unit #10 - #4
Two unit #14 - 1/0
Three unit #6 - 250 kcmil
Fuses
Protection is provided by 50,000 ampere interrupting capacity
current limiting fuses. A pop-up button on the fuse gives
visual indication of a blown fuse. GE recommends the use of
three fuses for the most complete protection against termi-
nal-to-terminal and terminal-to-ground failures on grounded
systems. Two fuses are sufficient to provide protection
against terminal-to-terminal failures on ungrounded systems.
Blown Fuse Lights
Blown fuse lights provide a positive external indication of an
operated fuse. A glowing light makes inspection of capacitors
easy, effective, and safe. A 120 VAC source must be supplied
externally. When ordered with this option, the HWT assembly
is supplied with one light per capacitor.
Fixed MV Power Factor Correction Capacitors