Specifications

26
Overall piping length 1,000m
Large diameter fan and DC motor has been utilized allowing an external static
pressure of 80Pa. This is approximately 2.6 times greater than the previous model.
80Pa
as standard
Previous model
V-II series
The outdoor unit can have a condenser hood easily connected with a static pressure of 80Pa standard.
This allows outdoor units to be installed within plant rooms in high rise buildings.
High static pressure of 80Pa
Powerful discharge
air prevents a short-circuit.
1,000m max.
Total pipe length
,
60m max.
Pipe length from first
separation tube to the
farthest indoor unit
50m max.
Height difference
between outdoor and
indoor units
15m max.
Height difference
between indoor and
indoor units
165m*
Actual pipe length
For the outdoor unit stated
below : 40m max. (Outdoor temp. -5°C)
5m max. (Outdoor temp. -5°C)
*: AIRSTAGE V-II
series is up to
150m.
27
High capacity connection
Installation in extreme temperature conditions is possible due to an
increase in operational range.
Wide operating range
FGL split type air-conditioner can be connected to VRF Network via
Network Convertor.
It is possible to manage the operation by using a FUJITSU VRF
control system.
Centralized control
*1. Conditions of maximum connectable indoor unit capacity ratio is as the chart below.
*2. Only 4HP is 46%
4HP-6HP
Connectable indoor unit
capacity range
50 % to 130%
*1
Connectable indoor
unit number
up to 8
4HP-6HP
Connectable indoor unit
capacity range
50 %
*2
to 130%
*1
Connectable indoor
unit number
up to 9
8HP-48HP
Connectable indoor unit
capacity range
50 % to 150 %
*1
Connectable indoor
unit number
up to 48
Connectable indoor unit
capacity range
50 % to 150 %
*1
Connectable indoor
unit number
up to 64
Outdoor unit capacity
8HP-48HP
4HP-6HP
Without 1.1kW models
Maximum connectable indoor unit capacity ratio
With 1.1kW models*
3
150%
130%
130%
117%(J-IIS), 120%(J-II)
*3. In the case of connectable indoor units, 1.1 kW models and Cassette and/
or Duct type of 9.0 kW class or more, maximum connectable indoor unit
capacity ratio is 110%.
Remote controller line
System Controller
RB Unit
Heat Recovery
VRF System
Single Split System
Network
Convertor
Heat Pump
Heat Pump
Heat Pump
AIRSTAGE
TM
J-IIS series
Heat Pump type
AIRSTAGE
TM
J-II series
Heat Pump type
AIRSTAGE
TM
V-II series
Heat Pump type
AIRSTAGE
TM
VR-II series
Heat Recovery type
AIRSTAGE
TM
J-IIS series
Heat Pump type
AIRSTAGE
TM
J-II series
Heat Pump type
AIRSTAGE
TM
V-II series
Heat Pump type
AIRSTAGE
TM
VR-II series
Heat Recovery type
(°C)
50
40
30
20
10
0
-10
-20
21°C
-20°C -20°C
Heating
-10°C -10°C
21°C
Cooling &
Heating
CoolingCooling
46°C
-10°C
-10°C
(°C)
50
40
30
20
10
0
-10
-20
21°C
-20°C
-20°C
Heating
CoolingCooling
46°C
-15°C *
4
-15°C *
4
21°C
-20°C -20°C
Heating
CoolingCooling
46°C
-5°C -5°C
(°C)
50
40
30
20
10
0
-10
-20
21°C
-20°C -20°C
Heating
CoolingCooling
46°C
-5°C -5°C
(°C)
50
40
30
20
10
0
-10
-20
*4. Note : When a multiple outdoor unit connection is used,
operating range is from -5°C to 46°C in cooling.