Specifications
1.1
1.3
38
510
400/470*1
320/440*1
0 to 90
25
26
21/25*1
20/22*1
ARXD04GALH
2.2
2.8
44
550
490
440
0 to 90
25
28
25
22
ARXD07GALH
Cooling
Heating
High
Med
Low
High
Med
Low
Liquid (Flare)
Gas (Flare)
Drain
Specifications
ARXD09GALH
2.8
3.2
50
600
550
480
0 to 90
25
29
26
24
ARXD14GALH
4.5
5.0
92
800
710
610
0 to 90
25
34
32
28
ARXD18GALH
5.6
6.3
83
940
840
750
0 to 90
25
34
32
28
198 x 900 x 620
22
ARXD24GALH
7.1
8.0
122
1,330
1,240
1,100
0 to 50
25
35
32
29
198 x 1,100 x 620
26
ARXD12GALH
3.6
4.0
54
600
510
450
0 to 90
25
30
27
24
kW
W
m
3
/h
Pa
dB(A)
mm
kg
mm
Model name
Power source
Capacity
Input power
Airflow rate
Static pressure range
Standard static pressure
Sound pressure level
Dimensions (H x W x D)
Weight
Connection
pipe diameter
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 27ÛCDB / 19ÛCWB, and outdoor temperature of 35ÛCDB / 24ÛCWB.
Heating : Indoor temperature of 20ÛCDB / (15ÛCWB), and outdoor temperature of 7ÛCDB / 6ÛCWB.
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
*1: This value is under cooling operation.
17 18
198 x 700 x 620
ø6.35
ø12.70
ø9.52
ø15.88
230V ~, 50Hz
ø25 (I.D.) ; ø32 (O.D.)
Slim design and wide range of
static pressure for flexible installation.
Models (With drain pump)
ARXD04GALH
ARXD07GALH
ARXD09GALH
ARXD12GALH
ARXD14GALH
ARXD18GALH
ARXD24GALH
Air-intake
Air intake direction can be selected
to match the installation site.
Back sideBottom side
Slim design
Drain port
This model is slim design, it can install
at the place where a ceiling is narrow.
Drain pump built-in
Drain pump
Slim Concealed Floor
ARXD04GALH
ARXD07GALH
ARXD09GALH
ARXD12GALH
ARXD14GALH
ARXD18GALH
ARXD24GALH
Indoor units
Height
198mm
64 65
65
Dimensions (Unit : mm)
Models: ARXD04 / ARXD07 / ARXD09 / ARXD12 / ARXD14 / ARXD18 / ARXD24
*Service accessibility must be allowed for when installing the product.
Please consult the installation manual for the necessary service access size.
ARXD04-14 ARXD18 ARXD24
700A
B
C
D
E
F
G
900
1100
650
850
1050
734
934
1134
650
850
1050
P100x6=600
P100x8=800
P100x10=1000
18xØ5
22xØ5
26xØ5
574
774
974
(Bolt pitch)
G
51
152
377
174
71
3030
F
(All surroundings)
82
48
E
D
C
(Bolt pitch)
43
31
198
168
78
B
A
10
69
144
264
367
620
47
55
78
89
119
163
Optional parts
Remote Sensor Unit :
IR Receiver Unit :
Auto Louver Grille Kit :
UTY-XSZX
UTB-YWC
UTD-GXSA-W
(for ARXD04/07/09/12/14GALH)
UTD-GXSB-W (for ARXD18GALH)
UTD-GXSC-W (for ARXD24GALH )
Drain hose is standard accessory
High lift drain pump
Filter (Accessory)
Filter
(2pcs.)
ARXD04 / 07 / 09 / 12 / 14 / 18 ARXD24
Filter
(3pcs.)
Selectable with a wide range of
static pressure
By using DC fan motor, it is possible
to change of static pressure range 0
to 90Pa.
The change of static pressure range
is possible by remote controller.
*24 model is 0 to 50Pa
Static pressure range
0 to 90 Pa
Flexible installation
Ceiling concealed
Floor concealed
Auto Louver Grille Kit (Option)
Slim Duct
Wired Remote
Controller
Wireles Remote
Controller
Auto Louver Grille
Simple flat Auto Louver will provide comfort airflow and harmonize
with luxury interior.
Max.
850mm