Specifications

114
Ventilation
Models
Control unit
UTY-VDGX
EEV unit
UTP-VX30A
UTP-VX60A
UTP-VX90A
DX-Kit for air handling applications
N E W
N E W
N E W
N E W
Multiple temperature sensors optimally control
the air handling unit and fan coil unit.
Wired R.C.
VRF system
Indoor
unit
EEV unit
Control unit
DX-Kit
Transmission line
Thermistor
Air Handling
Unit
Product’s image
AHU
Thermistor
DX-Kit
Thermistor
DX-Kit
FCU
DX Kit
ir handling uni
it
DX Kit
ha
nd
li
ng
u
ni
i
DX
K
it
handling
uni
A
H
U
DX
-K
it
m
m
m
m
Th
e
r
m
D
X-Ki
t
In case of connecting the air handling
unit, the supply air temperature is
controlled optimally by the discharge
temperature control.
In case of connecting the fan coil unit,
the room temperature is controlled
optimally by the intake temperature
control.
Control unit
UTY-VDGX
EEV unit
UTP-VX30A
EEV unit
UTP-VX60A
EEV unit
UTP-VX90A
• Central control from external controllers
AHU or FCU
(40 – 50 kW class)
Control unit
Piping
Wiring
Thermistor
External I/O
Transmission line
VRF Controller
Modbus network
Interface
(Option)
AHU or FCU
DX-Kit
External I/O
External I/O
3rd party
Controller
Transmission line
AHU or FCU
Thermistor
DDC*
*DDC=Direct Digital Controller
DX-Kit
A variety of controls to match the
application
Central control using our VRF controllers or central management
controllers
Supports a wide range of
capacity classes
2 EEV units can be connected in parallel and up to 20 HP (50
kW) large capacity units can be connected.
Connectable capacity range: 5 kW to 50 kW
This kit can connect the general-purpose air
handling unit (AHU) and the fan coil unit (FCU)
to the VRF system.
It enables VRF system to control the operation
of both air conditioner and ventilation.
Future release
11511
5
Specifications
Connectable Capacity class
Capacity
kW
Cooling
Heating
5.0kW 6.3kW 8.0kW 10.0kW 12.5kW 14.0kW 20.0kW 25.0kW 40.0kW 50.0kW
OutputsInputs
• ON/OFF
• Setting temperature
• Capacity demand
• Heating / Cooling operation mode
• Fault information
• ON/OFF indication
• Fan ON/OFF indication
• Thermo ON/OFF indication
• Defrost indication
• Fault indication
*Data were not available at time of production.
Note : Specifications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating : Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length : 7.5 m Voltage : 230 [V].
(Tentative)
Functions Summary
• Connectable VRF series : J-IIS, J-II, V-II, VR-II
• Connectable DX-Kit system capacity range : 50 to 100% of the
outdoor unit capacity
• Connectable DX-Kit system capacity range with indoor units :
30% or less of the outdoor unit capacity
• Max. wiring length from control unit : 15 m
• Max. piping length between EEV unit and indoor unit : 5 m
• Outdoor installation : Control unit (IP54 class) and EEV unit can
be installed at an outdoor space.
Installation Limitation
Air Handling Unit
Connectable capacity
• Single connection • Mixed connection
Within 30% of total capacity
50%100% of outdoor unit capacity
50%100% of outdoor unit capacity
Air Handling Unit
DX-KIt DX-KIt
Air Handling Unit
Piping and wiring length
Max. wiring length 15 m
Max. wiring length 15 m
Max. piping length 5 m
EEV unit
Control unit
Power source
Dimensions (H × W × D)
5.6
6.3
6.3
7.1
8.0
9.0
10.0
11.2
12.5
14.0
14.0
16.0
22.4
25.0
40.0
45.0
25.0
28.0
50.4
56.5
Control unit
V/Ø/Hz
mm
UTY-VDGX
230 / 1 / 50
*
Connection pipe diameter (Liquid)
Dimensions (H × W × D)
EEV unit
mm
mm
UTP-VX90A×2
Ø12.7
*
UTP-VX30A
Ø9.53
*
UTP-VX60A
Ø12.7
*
UTP-VX90A
Ø12.7
*