Specifications
Synergy Nano Technical Manual, Revision -
Page 239
UUT Module Sensor
When the UUT Module is selected, you can then
select which UUT module (second column), and
then the specific sensor on that module (third
column).
Press the Accept button when finished.
The Sensor Select Number Code will appear in
the Settings screen shown on the previous page.
This code is derived from the UUT Module
Sensor Code Chart shown below.
Important:
To use the UUT Module Sensor for cascade control, you must have the UUTs enabled. To enable UUTs, go
to the Comm\RS-485 folder, and change the RS-485 Mode from User Comms to UUT Sensors. You must
also set the Number of UUTs to the appropriate setting. See Section 13
for additional details.
UUT Module Sensor Code Chart
The Synergy Nano can accommodate up to four UUT modules, with up to sixteen sensors on each module.
UUT 1 UUT 2 UUT 3 UUT 4 UUT 5 UUT 6 UUT 7 UUT 8
Sensor 1 211 221 231 241 251 261 271 281
Sensor 2 212 222 232 242 252 262 272 282
Sensor 3 213 223 233 243 253 263 273 283
Sensor 4 214 224 234 244 254 264 274 284
Sensor 5 215 225 235 245 255 265 275 285
Sensor 6 216 226 236 246 256 266 276 286
Sensor 7 217 227 237 247 257 267 277 287
Sensor 8 218 228 238 248 258 268 278 288
Note: Since UUT modules have 16 sensors they respond to two sequential addresses. For example, a 16
Channel UUT module configured with an address of 1 will respond as UUT 1 and UUT 2. Sensors 1 thru 8
on the module will be reported as UUT 1, Sensors 1 thru 8. Sensors 9 to 16 on the module will be reported
as UUT 2, Sensors 1 thru 8.