Specifications

Synergy Nano Technical Manual, Revision -
Page 283
Setup the calibration the High Volts Scale for 5.0 VDC and Low Volts Scale for 1.0 VDC. Then
set the Engineering Scale for the specific sensor and scaling. Take a look at the input
calibration screen for the two examples below.
Example 1
J type thermocouple signal conditioner.
The output is -190 C for 4 mA (Low Scale)
and 760 C for 20mA (High Scale). The input
type is set to Temperature (Temp) as shown
at left.
Note that the High and Low Engineering
scale should be set in the current
temperature units of the controller. In this
example the signal conditioner range is
specified in C so the controller must be set in
units of C when entering these values
Example 2
Humidity Sensor, the signal conditioner
output is 4 mA for 0% RH and 20mA for
100% RH. The sensor type is set to
Vsla-RTD1, an uncompensated Vaisala
humidity sensor compensated with the
temperature reading from RTD1.
For additional information regarding calibration see the Setup section 6.0
of this manual.