Specifications

Synergy Nano Technical Manual, Revision -
Page 307
Description Command Root Command
Usages
Command Syntax Range,
Units
Command
Example
Response Example
Rate Band,
Ch 3 Cool
RB3C RB3C Set = RB3C ARG1 1 - 60 Seconds = RB3C 4 OK
RB3C Query ? RB3C 1 - 60 Seconds ? RB3C 4.000
Celsius /
Fahrenheit
Temp Display
CF CF Set = CF ARG1 ARG1:
0 - Celsius
1 - Fahrenheit
= CF 0 OK
CF Query ? CF 0 - Celsius
1 - Fahrenheit
? CF 0
Output 11
Control Type
OT11 OT11 Set = OT11 ARG1 ARG1:
0 - On / Off Control Mode
1 - Time Prop. Control Mode
= OT11 0 OK
OT11 Query ? OT11 0 - On / Off Control Mode
1 - Time Prop. Control Mode
? OT11 0
Output 17
Control Type
OT17 OT17 Set = OT17 ARG1 ARG1:
0 - Vacuum
1 - Purge
= OT17 1 OK
OT17 Query ? OT17 0 - Vacuum
1 - Purge
? OT17 1
Output 18
Control Type
OT18 OT18 Set = OT18 ARG1 ARG1:
0 - Vent
1 - Boost Cool
= OT18 1 OK
OT18 Query ? OT18 0 - Vent
1 - Boost Cool
? OT18 1
Alarm Type ATYP ATYP Set = ATYP ARG1 ARG1:
0 - Process Alarm
1 - Deviate Alarm
= ATYP 1 OK
ATYP Query ? ATYP 0 - Process Alarm
1 - Deviate Alarm
? ATYP 1
Low Limit, Ch
1
R1L R1L Set = R1L ARG1 - 200 to 500 C -326 to 932 F = R1L -200 OK
R1L Query ? R1L - 200 to 500 C -326 to 932 F ? R1L -200
High Limit,
Ch 1
R1H R1H Set = R1H ARG1 - 200 to 500 C -326 to 932 F = R1H 500 OK
R1H Query ? R1H - 200 to 500 C -326 to 932 F ? R1H 500
Low Limit, Ch
2
R2L R2L Set = R2L ARG1 - 200 to 500 %RH = R2L -1 OK
R2L Query ? R2L - 200 to 500 %RH ? R2L -1
High Limit,
Ch 2
R2H R2H Set = R2H ARG1 - 200 to 500 %RH = R2H 100 OK
R2H Query ? R2H - 200 to 500 %RH ? R2H 100