Specifications

Synergy Nano Technical Manual, Revision -
Page 331
Description Command Root Command
Usages
Command Syntax Range,
Units
Command
Example
Response Example
Log UUT8
Readings
LOG_UUT8 LOG_UUT8 Set = LOG_UUT8 ARG1 ARG1:
0 - Don't Log
1 - Log
= LOG_UUT8 1 OK
LOG_UUT8
Query
? LOG_UUT8 0 - Don't Log
1 - Log
? LOG_UUT8 0
Log Outputs LOG_OUTPU
TS
LOG_OUTPUTS
Set
= LOG_OUTPUTS ARG1 ARG1:
0 - Don't Log
1 - Log
= LOG_OUTPUTS 1 OK
LOG_OUTPUTS
Query
? LOG_OUTPUTS 0 - Don't Log
1 - Log
? LOG_OUTPUTS 0
PID Channel 1
Heat *
PID1H PID1H Query ? PID1H 1 - 100 % ? PID1H 0.0
PID Channel 1
Cool *
PID1C PID1C Query ? PID1C 1 - 100 % ? PID1C 100.0
PID Channel 2
Heat *
PID2H PID2H Query ? PID2H 1 - 100 % ? PID2H 0.0
PID Channel 2
Cool *
PID2C PID2C Query ? PID2C 1 - 100 % ? PID2C 100.0
PID Channel 3
Heat *
PID3H PID3H Query ? PID3H 1 - 100 % ? PID3H 0.0
PID Channel 3
Cool *
PID3C PID3C Query ? PID3C 1 - 100 % ? PID3C 100.0
Acknowledge All
Alarms *
ACKALM ACKALM Set = ACKALM ARG1 ARG1 - Always 1 to reset the alarms
Number of active alarms, 32 bit hex
number representing types of alarms.
= ACKALM 1 0, 00000001
Show Active
Alarms *
SHOWACTA
LM
SHOWACTALM
Query
? SHOWACTALM Shows all active alarms.
Number of active alarms, 32 bit hex
number representing types of alarms.
? SHOWACTALM 0, 00000001
Show Alarm
Status *
ALM ALM Query ? ALM Shows alarm states
Returns 3 values: %i, %i, %8.8X
First: Number of Alarms, both active
& inactive
Second: Number of active alarms
Third: 32 bit hex number with each
bit representing a different alarm
? ALM 0, 0, 00000000