RTD Calibration
♦ This screen is used to enter an offset and
gain for the raw data in Ohms. This can
be used to compensate for a difference in
the reading due to sensor position, wiring,
etc.
♦ Select Type and press Change to select
the RTD Sensor type from the list.
RTD Calibration
♦ Sensor Type
♦ This screen is used to select the RTD
Type from the following list.
RTD JIS 500
RTD JIS 100
RTD DIN 500
RTD DIN 100
Note: In early software versions, the RTD curves
were set globally so one RTD curve was used
for both sensors.
6.2.4.2 Analog Voltage Calibration
Each of the controller’s analog inputs is calibrated and scaled from this folder. The Raw Calibration
parameter is used to calibrate the physical voltage measurement. The voltage scale and engineering scale
are used to scale the value to engineering units. These inputs can be scaled to select a wide range of signal
conditioners with 0-5VDC and 4-20mA outputs. In addition, when set to the Temperature Type, the Synergy
Nano converts inputs from C to F and vice versa.
Calibration Hi Res Analog 1 thru 4
♦ This screen is used to enter Raw
Calibration data, Voltage and Engineering
scales.
♦ Select Raw Calibration then press Change
button