Specifications

Synergy Nano Technical Manual, Revision -
Page 60
L-Value Descriptions
L-Values are parameters for the programmable logic that control processes in the Device Primitives. Flow
charts illustrating the Device Primitives are illustrated in Section 6.7 Device Primitives
of this manual. Please
refer to the Device Primitives flow charts in conjunction with the definitions below when editing L-Values.
1L1 Ch1 Main Cooling Turn-On
Cooling output required to turn on channel 1 cooling. (0 to 100%)
1L2 Ch1 Main Cooling Turn-Off
Heat output required to turn off channel 1 main cooling. (-100 to 100%)
1L3 Ch1 Setpoint Transfer Setting
Temperature threshold that enables artificial load device. (-100 to 100C, -148 to 212F)
1CTY Ch1 Chamber Type
Defines the controlling logic for channel 1. (CAP Tube System, Agree Logic, Burn-in Logic, XV Sys Logic)
2L1 Ch2 Main Cooling Turn-On
Cooling output required to turn on channel 2 cooling. (0 to 100%)
2L2 Ch2 Main Cooling Turn-Off
Heat output required to turn off channel 2 main cooling. (0 to 100%)
2L3 Ch2 Setpoint Transfer Setting
Temperature value that enables artificial load device. (-100 to 100C, -148 to 212F)
2CTY Ch2 Chamber Type
Defines the controlling logic for channel 1. (CAP Tube System, Agree Logic, Burn-in Logic, XV Sys Logic)
L3 Ch1 Main Cooling Turn-On
Percent cooling value that turns on the low stage compressor. (0 to 100%)
L4 Ch1 Main Cooling Turn-Off
Percent heat required before turning off low stage compressor. (0 to 100%)
L6 Full Cooling Switch-Over
Full cooling is switched on at this temperature. (-100 to 100C, -148 to 212F)
L7 Ambient Cooling Turn-On
Percent cooling required that turns on the compressor. (0 to 100%)
L8 Heat Ambient Cooling Turn-Off
Percent heat required to turn off the compressor. (0 to 100%)
L9 Ramp-up Cooling
The temperature value that turns off the cooling compressor while heating. (-100 to 100C, -148 to 212F)
L11 Dehumidify / Vent On
Percent dehumidify required to enable dehumidify device. (0 to 100%)
L12 Dehumidify / Vent Off
Percent humidify required to turn off dehumidify device. (0 to 100%)
L14 Time Delay Boost Cool
Time delay required before Boost Cool is enabled. (0 to 1200 seconds)