Specifications

Synergy Nano Technical Manual, Revision -
Page 64
6.7 Device Primitives and Logic Flow Charts
The following flow charts explain the function and the logic that drives each output device. Note that
chambers don’t have every device. For example, Temp-Only chambers will not have humidity related
devices such as the Wick Pan. These flow charts have extensive references to the L-Values described in
the previous sections.
You can monitor the state of each output and the performance based upon the L-Value settings by going to
the Events\Digital Outputs screen while the chamber is running. For more information on the Digital Outputs
screen, go to Section 11.3 Events: Digital Outputs
.
Note: The output from each device is dependent upon the chamber configuration. See Section 6.10 Setup:
Output Mappings by Chamber Type to determine the controller’s outputs in your specific configuration.
Device Primitives Key
Fan Device
Drives the Fan. This output is on whenever the chamber is running.
Output is On/Off