Specifications
Synergy Nano Technical Manual, Revision -
Page 68
Low Artificial Load
This output energizes the Artificial Loading bypass solenoid to provide refrigerant flow to the compressor
when operating with temperature control only.
Output is Time Proportioning the inverse of the PID Cool output
Affected By: Default Value: Range:
Channel 1 Proportional Band Cooling 5 0 - 50 Degrees C
Reset for Channel 1 Cooling 0.07 0 - 9.9 Repeats/minute
Rate for Channel 1 Cooling 0 0 - 9.9 Minutes
Cycle Time for Channel 1 Cooling 7 1 - 60 Seconds
Rate Band for Channel 1 Cooling 0 0 - 7 Seconds
High Artificial Load
Output is On/Off
Compressor Cut In Logic (Input 3) When closed, selects Compressor Cut In Logic. Uses a
pressure switch
There is a one-minute turn on timer that is reset while the compressor is off.
Output mirrors the High Stage Compressor