Specifications
Synergy Nano Technical Manual, Revision -
Page 83
Nano Temp Only
Main Screen
Digital Output Screen
Channels
Inputs Channel 1 Channel 2 Channel 3 Channel 4
Type Temperature N/A N/A N/A
Sensor RTD1 N/A N/A N/A
High Volt Scale N/A N/A N/A N/A
Low Volt Scale N/A N/A N/A N/A
High Eng Scale N/A N/A N/A N/A
Low Eng. Scale N/A N/A N/A N/A
Digital Inputs
Name Input Function when Closed
Compressor Cut in Logic Input 3 Boost Heat, High Artificial Load, High Stage Compressor, Cascade
Condenser (See Section 6.7 Device Primitives
etc)
Burn-in Logic Input 4 Enables Low Stage Compressor and Full Cool with LEV1.
AGREE Chamber Logic Input 5 Locks out Low Stage Compressor and enables High Stage
Compressor and Full Cool with LEV1
TempGard Input 9 None, TempGard Alarm displays in Alarm Folder and Log File.
Alarms
Name Sensor Sensor
Code
Default
Threshold
Report Log K1 K2
Hi Alarm Ch 1 RTD1 110 > 500 C Yes Yes Yes No
Low Alarm Ch 1 RTD1 110 < -200C Yes Yes Yes No
Bad Sensor Ch 1 RTD1 110 < 10 Ohm Yes Yes Yes No
Bad Sensor Ch 1 RTD1 110 > 330 Ohm Yes Yes Yes No
TempGard Digital Input 9 409 Open Yes Yes No No