Technical information
1/2
1SDC210033D0202
XT1
Size
(G2.1)
[A] 160
Poles [No.] 3, 4
Rated service voltage, Ue
(G2.4)
(AC) 50-60Hz [V] 690
(DC) [V] 500
Rated insulation voltage, Ui
(G2.5)
[V] 800
Rated impulse withstand voltage, Uimp
(G2.6)
[kV] 8
Versions Fixed, Plug-in
(2)
Breaking capacities according to IEC 60947-2 B C N S H
Rated ultimate short-circuit breaking capacity, Icu
(G2.7)
Icu @ 220-230-240V 50-60Hz (AC) [kA] 25 40 65 85 100
Icu @ 380V 50-60Hz (AC) [kA] 18 25 36 50 70
Icu @ 415V 50-60Hz (AC) [kA] 18 25 36 50 70
Icu @ 440V 50-60Hz (AC) [kA] 15 25 36 50 65
Icu @ 500V 50-60Hz (AC) [kA] 8 18 30 36 50
Icu @ 525V 50-60Hz (AC) [kA] 6 8 22 35 35
Icu @ 690V 50-60Hz (AC) [kA] 3 4 6 8 10
Icu @ 250V (DC) 2 poles in series [kA] 18 25 36 50 70
Icu @ 500V (DC) 2 poles in series [kA] – – – – –
Icu @ 500V (DC) 3 poles in series
(3)
[kA] 18 25 36 50 70
Rated service short-circuit breaking capacity, Ics
(G2.8)
Ics @ 220-230-240V 50-60Hz (AC) [kA] 100% 100% 75% (50) 75% 75%
Ics @ 380V 50-60Hz (AC) [kA] 100% 100% 100% 100% 75%
Ics @ 415V 50-60Hz (AC) [kA] 100% 100% 100% 75% 50% (37.5)
Ics @ 440V 50-60Hz (AC) [kA] 75% 50% 50% 50% 50%
Ics @ 500V 50-60Hz (AC) [kA] 100% 50% 50% 50% 50%
Ics @ 525V 50-60Hz (AC) [kA] 100% 100% 50% 50% 50%
Ics @ 690V 50-60Hz (AC) [kA] 100% 100% 75% 50% 50%
Ics @ 250V (DC) 2 poles in series [kA] 100% 100% 100% 100% 75%
Ics @ 500V (DC) 2 poles in series [kA] – – – – –
Ics @ 500V (DC) 3 poles in series
(3)
[kA] 100% 100% 100% 100% 75%
Rated short-circuit making capacity, Icm
(G2.10)
Icm @ 220-230-240V 50-60Hz (AC) [kA] 52.5 84 143 187 220
Icm @ 380V 50-60Hz (AC) [kA] 36 52.5 75.6 105 154
Icm @ 415V 50-60Hz (AC) [kA] 36 52.5 75.6 105 154
Icm @ 440V 50-60Hz (AC) [kA] 30 52.5 75.6 105 143
Icm @ 500V 50-60Hz (AC) [kA] 13.6 36 63 75,6 105
Icm @ 525V 50-60Hz (AC) [kA] 9.18 13.6 46.2 73.5 73.5
Icm @ 690V 50-60Hz (AC) [kA] 4.26 5.88 9.18 13.6 17
Breaking capacities according to NEMA-AB1
@ 240V 50-60Hz (AC) [kA] 25 40 65 85 100
@ 480V 50-60Hz (AC) [kA] 8 18 30 36 65
Utilisation Category (IEC 60947-2) A
Reference Standard IEC 60947-2
Isolation behaviour
Mounted on DIN rail DIN EN 50022
Mechanical life
(G2.14)
[No. Operations] 25000
[No. Hourly operations] 240
Electrical life @ 415 V (AC)
(G2.13)
[No. Operations] 8000
[No. Hourly operations] 120
Dimensions - Fixed
(Width x Depth x Height)
H
W
D
3 poles [mm] 76.2 x 70 x 130
4 poles [mm] 101.6 x 70 x 130
Total opening time
Circuit-breaker with shunt opening release [ms] 15
Circuit-breaker with undervoltage release [ms] 15
Trip units for power distribution
TMD/TMA
TMD
Q
Ekip LS/I
Ekip I
Ekip LSI
Ekip LSIG
Ekip E
Trip units for motor protection
MF/MA
Ekip M-I
Ekip M-LIU
Ekip M-LRIU
Trip units for generator protection
TMG
Ekip G-LS/I
Trip units for oversized Neutral Protection
Ekip N-LS/I
Interchangeable protection trip units
Weight Fixed 3/4 poles [kg] 1.1 / 1.4
Plug in (EF terminals) 3/4 poles [kg] 2.21 / 2.82
Withdrawable (EF terminals) 3/4 poles [kg]
(1)
90kA@690V only for XT4 160. Available shortly, please ask ABB SACE
(3)
XT1 500V DC 4 poles in series Q Complete circuit-breaker
(2)
XT1 plug-in In max=125A
(4)
XT4 750V DC please ask ABB SACE for availability V Loose trip unit
Construction characteristics