Technical information

4/31
1SDC210033D0202
Magnetic Trip Values
Breaker Trip Unit In
[A]
I
3
[A]
Single-phase trip current
(%I
3
)
(1)
XT1 TMD 16..160 450..1600 150%
XT2
MF/MA 1..100 14..1400 150%
TMD/TMA 1.6..160 16..1600 150%
TMG 16..160 160..480 150%
Ekip I 10..160 1..10xIn 100%
Ekip LS/I 10..160 1..10xIn 100%
Ekip LSI 10..160 1..10xIn 100%
Ekip LSIG 10..160 1..10xIn 100%
Ekip M-I 20..100 6..14xIn 100%
Ekip M-LIU 25..100 6..13xIn 100%
Ekip M-LRIU 25..100 6..13xIn 100%
Ekip G-LS/I 10..160 1..10xIn 100%
Ekip N-LS/I 10..100 1..10xIn 100%
XT3
MA 100..200 600..2400 150%
TMD 63..250 630..2500 150%
TMG 63..250 400..750 150%
XT4
MA 10..200 50..2000 150%
TMD/TMA 16..250 300..2500 150%
Ekip I 40..250 1..10xIn 100%
Ekip LS/I 40..250 1..10xIn 100%
Ekip LSI 40..250 1..10xIn 100%
Ekip LSIG 40..250 1..10xIn 100%
Ekip M-LIU 40..160 6..13xIn 100%
Ekip M-LRIU 40..200 6..13xIn 100%
Ekip G-LS/I 40..250 1..10xIn 100%
Ekip N-LS/I 40..160 1..10xIn 100%
Ekip E-LSIG 40..250 1..10xIn 100%
(1)
Satisfies the requirements of the IEC 60947-2 Standard, section 8.3.3.1.2