Technical information
5/119
1SDC210033D0202
Overall dimensions
Distances to be respected
Insulation distances for installation in metallic cubicle
Minimum center distance between two circuit-breaker side-by-side
Minimum centre distance for superimposed circuit-breakers
Ue)440V AC
Ue)250V DC
A
(mm)
B
(mm)
C
(mm)
XT1
25 20 20
XT2
30 10 25
XT3
50 20 20
XT4
30 20 25
Ue>440V AC
A
(mm)
B
(mm)
C
(mm)
XT1
25 20 20
XT2
50 20 45
XT3
50 20 20
XT4
50 20 45
250<Ue)500V DC
A
(mm)
B
(mm)
C
(mm)
XT1
25 20 20
XT2
50 50 45
XT3
50 20 20
XT4
50 50 45
Circuit-breaker width
(mm)
Centre distance I
(mm)
3 poles 4 poles 3 poles 4 poles
XT1
76 102 76
(*)
102
(*)
XT2
90 120 90
(*)
120
(*)
XT3
105 140 105 140
XT4
105 140 105
(*)
140
(*)
(*)
with phases separator between two circuit-breakers
H
(mm)
XT1
80
XT2
100
XT3
140
XT4
150
Caption
1 Connection - not insulated
2 Insulated cable
3 Cable terminal