Circuit-breakers for power distribution
Electronic trip units
Ekip I
Main characteristics:
Q usable with the XT2 and XT4 circuit-breaker in the three-pole and four-pole versions;
Q protections:
against instantaneous short-circuit (I): adjustable protection threshold from 1...10xIn, with
instantaneous trip curve;
of the neutral in four-pole circuit-breakers:
- for In*100A in the OFF or ON positions, 50% and 100% of the phases can be selected;
- for In<100A, neutral protection is fi xed at 100% of the phases and disableded by user;
Q manual setting using the relative dip-switches, which allow the settings to be made even when
the trip unit is off;
Q LED:
LED lit with a steady green light indicating that the trip unit is supplied correctly. The LED
comes on when the current exceeds 0.2xIn;
LED with a steady red light, indicating that protection I has tripped; red LED light on connect-
ing Ekip TT or Ekip T&P accessories after circuit-breaker opening for “I protection” interven-
tion;
Ekip I is equipped with a trip coil disconnection protection device that detects whether the
opening solenoid has disconnected. Signalling is made by the red LED fl ashing;
Q test connector on the front of the trip unit;
to connect the Ekip TT trip test unit, which allows trip test, LED test and signalling about
latest trip happened;
to connect the Ekip T&P unit, which allows the measurements to be read, the trip test to be
conducted and the I protection function test to be carried out;
Q self-supply from a minimum current of 0.2xIn up.
Ekip I
Protection function Trip threshold Trip curve
(1)
Excludability Relation
Against short-circuits with
adjustable treshold and
instantaneous trip time
Manual setting:
I
3
= 1, 1.5, 2, 2.5, 3, 3.5, 4.5,
5.5, 6.5, 7, 7.5, 8, 8.5, 9,
10xIn
Tolerance: ±20% I>4In
±10% I)4In
)20ms Yes t = k
I protection LED
Test Connector
Dip switch for I protection
function setting
Power-on LED
(1)
Tollerances in case of:
– self-powered trip unit at full power;
– 2 or 3 phase power supply.
In conditions other than those considered, the trip time is
)60ms
.
Slot for lead seal