Technical information

2/20
1SDC210033D0202
Q with the addition of the Ekip Com in the circuit-breaker, you can:
acquire and transmit a wide range of information via remote control;
accomplish the circuit-breaker opening and closing commands by means of the motor
operator in the electronic version (MOE-E);
know the state of the circuit-breaker (open/closed/trip) via remote control;
setting the confi guration and programming parameters of the unit, such as the current thresh-
olds and the protection function curves.
Ekip M-LRIU
Protection function
Trip threshold Trip curve
(1)
Excludability Relation Thermal
memory
Against overloads with
long inverse time delay trip
according to IEC 60947-4-1
Manual setting:
I
1
= 0.4...1xIn step 0.04
Tolerance:
trip between 1.05...1.2xI
1
Manual setting:
Trip class: 3E, 5E, 10E, 20E
Tolerance: ±10% up to 4xIn
±20% from 4xIn
t = k/l
2
Yes
Electronic setting:
I
1
= 0.4...1xIn step 0.01
Tolerance:
trip between 1.05...1.2xI
1
Electronic setting:
Trip class: 3E, 5E, 10E, 20E
Tolerance: ±10% up to 4xIn
±20% from 4xIn
t = k/l
2
Yes
R
Against rotor block with
delayed trip and with an
indipendent time delay trip
(IEC 60947-4-1)
Manual setting:
I
5
= OFF, 3, 6, 9xI
1
Tolerance: ±10%
Manual setting: t
5
= 1, 4s
±20% from 4xIn
Yes t = k
Electronic setting:
I
5
= OFF, 3...9xI
1
step 0.1I
1
Tolerance: ±10%
Electronic setting:
t
5
=1...4s step 0.5
Tolerance: ±10% up to 4xIn
±20% from 4xIn
Yes t = k
Against short-circuits
threshold with adjustable
threshold and istantaneous
trip time
Manual setting:
I
3
= 6-8-11-13xIn
Tolerance: ±10%
)40ms t = k
Electronic setting:
I
3
= 1...13xIn
Tolerance: ±10%
)40ms t = k
Aganist phase current
unbalanced or loss of phase
with tripping at indipendent
time (IEC 60947-4-1)
Manual setting:
I
6
= On / Off
When ON, I
6
= 50% I
1
Tolerance: ±15%
Manual setting:
t
6
= 2s
Tolerance: ±20%
Yes t = k
Electronic setting:
I
6
= On / Off
When ON, I
6
= 10%..50% I
1
step
10% I
1
Tolerance: ±15%
Electronic setting:
t
6
= 0...5s step 0.5
Tolerance: ±20%
Yes t = k
Against earth fault with
indipendent time delay trip
(2)
Electronic setting:
I
4
= 0.2...1xIn step 0.1In
Tolerance: ±10%
Electronic setting:
t
4
= 0.1...0.8s step 0.01
Tolerance: ±15%
Yes t = k
L, R, I, U protection LED
Test connector
Dip switch for L protection
function setting
Power-on LED
Dip switch for R protection function setting
Dip switch for the trip
classes setting according
to IEC 60947-4-1
U protection function ON-OFF
LED for Electronic/Manual setting
Dip switch for I protection
function setting
Dip switch for the trip curve selection
R protection function ON-OFF
Setting MAN/ELT
(1)
Tollerances in case of:
– self-powered trip unit at full power;
– 2 or 3 phase power supply.
In conditions other than those
considered, the following tollerance hold:
Protection Trip threshold Trip time
L
release between 1.05 and 1.2 x I
1
±20%
R
±20% ±20%
I
±20% )60ms
U
±20% ±20%
G
±15% ±20%
Slot for lead seal
(2)
Protection G is inhibited for currents higher than
2 In.
Circuit-breakers for motors protection
Electronic trip units
Tolerance: ±10% up to 4xIn