Technical information
2/31
24 V
+
–
+
Modbus
24 V
+
–
+
HMI030
Modbus
Internal Bus
1SDC210033D0202
Configuration 2: Supervision and Remote control (Thermomagnetic trip unit or switch-
disconnector, Ekip Com and MOE-E)
The Ekip Com accessory, positioned in the right-hand slot of the circuit-breaker, is connected with
the MOE-E by means of the connector on the rear of the MOE-E.
Six cables come out of the Ekip Com, of which two are needed for the auxiliary power supply and
two for connection to the Modbus.
With this configuration it is possible to:
Q read the Open/Closed/Tripped state of the circuit-breaker remotely;
Q open/close the circuit-breaker or of the switch-disconnector remotely.
For further details regarding cabling of the various devices, please refer to the chapter on Electric
Diagrams.
Configuration 3: Supervision and Remote Control (Electronic trip unit, Ekip Com and MOE-E)
Positioned in the right-hand slot of the circuit-breaker, the Ekip Com accessory connects to the Ekip
LSI, Ekip LSIG, Ekip E-LSIG or Ekip M-LRIU trip unit via connector supplied with Ekip Com and to
the MOE-E via connector be present on MOE-E behind. Six cables come out of Ekip Com of which
two are required for auxiliary supply, two for connection to the Modbus and two for connection to
Internal Bus.
This configuration allows you to:
Q read the measurements and settings from the solid-state release in remote mode;
Q program the electronic trip unit in remote mode;
Q read the state of the circuit-breaker (Open/Closed/Tripped) in remote mode;
Q open/close the circuit-breaker in remote mode;
Q visualize locally on HMI 030 all the relevant information of the CB.
Consult the Electric Diagrams chapter for further details about wiring.