Technical information

2/32
24 V
+
EP010
+
Modbus
HMI030
Modbus
Internal Bus
1SDC210033D0202
Configuration 4: EP010 - Fieldbus Plug (Electronic trip unit, Ekip Com and EP010)
Positioned in the right-hand slot of the circuit-breaker, the Ekip Com accessory connects to the Ekip
LSI, Ekip LSIG, Ekip E-LSIG or Ekip M-LRIU trip unit via connector supplied and to the MOE-E via
connector be present on MOE-E behind (MOE-E connection is optional for this configuration). Six
cables come out of Ekip Com, of which two are required for auxiliary supply, two for connection to
the EP010 and two for connection to Internal Bus.
Connection of the EP010 to the network is to be made by the Customer and depends on the Field-
bus plug connector used.
With this configuration, it is possible to:
Q make the SACE Tmax XT circuit-breakers communicate in a network with Profibus or Devicenet
comunication protocol;
Q read the measurements and settings from the solid-state release in remote mode;
Q program the electronic trip unit in remote mode;
Q read the state of the circuit-breaker (Open/Closed/Tripped) in remote mode;
Q open/close the circuit-breaker in remote mode;
Q visualize locally on HMI 030 all the relevant information of the CB.
Special applications
Communication system
Connector is to be provided by the Customer
(PDP22 for Profibus, DNP21 for Devicenet)