3/2
1SDC210033D0202
Accessories
Versions and types
Tmax XT automatic circuit-breakers are available in the following versions:
Q
FIXED. Fixed circuit-breakers consist of a current-interrupting part connected to the trip unit, to
be installed on the back plate of the cubicle or on a DIN rail;
Q
PLUG-IN. Plug-in circuit-breakers consist of a fixed part that must be installed on the back plate
of the cubicle, and of a moving part, obtained from the fixed circuit-breaker plus the relative kit
that converts it from the fixed version into the moving part of the plug-in version;
Q
WITHDRAWABLE. Withdrawable circuit-breakers consist of a fixed part that must be installed
on the back plate of the cubicle equipped with side runners to allow the moving part to be eas-
ily racked out and in, winch is obtained from the fixed circuit-breaker plus the relative kit that
converts it from the fixed version into the withdrawable moving part. To obtain the withdrawable
version, a front accessory to be applied onto the front of the circuit-breaker must be ordered so
as to maintain the IP40 degree of protection over the entire isolation run of the circuit-breaker.
If the plug-in circuit-breaker is fitted with electrical accessories, the appropriate connectors for isola-
tion of the relative auxiliary circuits must also be ordered on the other hand, for the withdrawable
version there are dedicated accessories, fitted with connectors which allow automatic disconnec-
tion in the case of racking-out (consult the “connection of electrical accessories” section in the
Accessories chapter).
Starting from the fixed version, SACE Tmax XT circuit-breakers can easily be converted into the
plug-in and withdrawable versions using the relative conversion kits.
The moving part can always be obtained in the required version, fully pre-engineered in the factory,
by ordering the fixed circuit-breaker and the conversion kit at the same time.
Version
Fixed Plug-in Withdrawable
XT1
QQ
XT2
QQQ
XT3
QQ
XT4
QQQ
Fixed part of plug-in and withdrawable versions
The fixed parts of the plug-in/withdrawable versions are available with front terminals (F) or with
horizontal or vertical rear terminals (HR/VR). The terminals are factory-mounted in the horizontal po-
sition. In case of need, the Customer can easily rotate the terminals into the vertical position. These
fixed parts can be equipped with the same terminal, terminal-cover and phase separator kits used
for the fixed circuit-breakers, using the proper adapter.
The fixed parts of a plug-in/withdrawable circuit-breaker can be installed at a distance of 50mm
from the back of the panel or at 70mm as shown in the picture. Installation at 50mm is only compul-
sory in the case where rear vertical or horizontal terminals (HR/VR) are used.
Fixed circuit-breaker
Plug-in circuit-breaker
Withdrawable circuit-breaker
Fixing at 50mm
Fixing at 70mm