Technical information
3/5
1SDC210033D0202
Mechanical Accessories XT1 XT2 XT3 XT4
Terminals
F- Front
QQQQ
EF - Front extended
QQQQ
ES - Front extended spread
QQQQ
FCCu - Front for copper cables
QQQQ
FCuAl - Front for copper/aluminium cables
QQQQ
FB - For flexible busbars
QQQQ
MC - Multi-cable
QQQQ
R - Rear orientated
QQQQ
EF - Extended front for the fixed part
QQQQ
HR/VR - Horizontal rear / Vertical rear for
fixed part
QQQQ
HR for RC - for residual current release
Q
–––
Rotary handle operating
mechanism
RHD - Direct rotary handle
QQQQ
RHE - Transmitted rotary handle
QQQQ
RHE-LH - Wide transmitted rotary handle
QQQQ
RHS - Side rotary handle
QQQQ
Front for lever operating mechanism FLD - Front for locks
–
Q
–
Q
Locks on CB
Padlock device
QQQQ
Key lock
QQQQ
Locks on handle Key lock
QQQQ
Locks on FLD Key lock
–
Q
–
Q
Locks on Motor Operator
Key lock
QQQQ
Key lock against manual operation
–
Q
–
Q
Look for fixed part Key lock
–
Q
–
Q
Rear interlock Interlock
QQQQ
Bracket for DIN rail Bracket
QQQQ
Consult the relative section for more details.
Connection terminals
Connection terminals allow the circuit-breaker to be connected to the system in the way most suited
to the installation requirements. By and large they consist of:
Q
front terminals: for connecting cables or busbars directly from the front of the circuit-breaker;
Q
rear terminals: for installing circuit-breakers in segregated panels with rear access.
Where possible, the terminals have laser marking on the surface indicating the tightening torques for
the correct isolation of cables and bars.
Fixed version
The part of the standard equipment, fixed version SACE Tmax XT circuit-breakers are supplied with
front terminals (F). However, they can be fitted with the following types of terminals as accessories
thanks to the special kits:
Q
extended front (EF);
Q
extended spread front (ES);
Q
front for copper/aluminium cables (FCCuAI). A pitch adapter must be applied to the terminal
zone of the circuit-breaker to ensure that copper and aluminium cables with sections of up
to 240mm
2
can be connected to all the circuit-breakers. The pitch adapter is automatically
supplied when it is necessary (see table page 3/9);
Q
front for copper cables (FCCu);
Q
for flexible busbars (FB);
Q
multicable (MC);
Q
rear oriented (R).
Accessories
Mechanical Accessories