Technical information
3/21
1SDC210033D0202
Cabled auxiliary contact
Cabled auxiliary contact for
withdrawable circuit-breaker
AUX 250V AC/DC - Electrical specifications
Power supply Voltage
[V]
Class of use
(G2.16)
Operating current [A]
AC DC
110 AC/DC
DC-12 – 0.5
DC-14 – 0.05
125 AC/DC
AC-12, AC-13, AC-14 6 –
AC-15 5 –
250 AC/DC
AC-12 and DC-12 6 0.3
AC-13 6 –
AC-14 and DC-14 5 0.03
AC-15 4 –
AUX 24V DC - Electrical specifications
Power supply Voltage
[V]
Operating current [A]
DC
5 DC 0.01
24 DC 0.1
400V AC auxiliary contacts
400V AC auxiliary contacts are only available for XT2 and XT4 circuit-breakers in the following
versions:
Q
cabled (AWG17 cable section -1mm
2
):
– for fi xed/plug-in circuit-breakers with 1m long cables;
– for withdrawable circuit-breakers with fi xed part and moving part connector.
The 400V auxiliary contacts take up the whole right-hand slot of the circuit-breaker.
Combinations
XT1 XT2 XT3 XT4
3/4p 3/4p 3/4p 3/4p
1Q 1SY 400V – F-P-W – F-P-W
2Q 400V – F-P-W – F-P-W
F = Fixed, P = Plug-in, W = Withdrawable
Auxiliary contacts 400V AC
Circuit-breaker 3p Circuit-breaker 4p
XT2
XT4
AUX
400V
AUX
400V
AUX 400V AC - Electrical specifications
Power supply Voltage
[V]
Operating current [A]
AC DC
125 AC/DC – 0.5
250 AC/DC 12 0.3
400 AC/DC 3 –