Outback Power Integration Guide

REV042920
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com| SimpliPhiPower.com
| 17 |
PHI 2.7-25.6V
nom
45 1,152
1,355
5.6
11.3
PHI 2.6-25.6V
nom
45 1,152
1,355
5.6
11.3
PHI 1.4-25.6V
nom
28.5 730
858
3.6
7.2
PHI 1.3-25.6V
nom
26 666
783
3.3
6.5
PHI 1.4-12.8V
nom
45 576
678
2.8
5.6
PHI 1.3-12.8V
nom
40 512
602
2.5
5.0
PHI 730-25.6V
nom
14 358
422
1.8
3.5
PHI 675-25.6V
nom
13 333
392
1.6
3.3
PHI 730-12.8V
nom
28.5 365
429
1.8
3.6
PHI 675-12.8V
nom
26 333
392
1.6
3.3
4.3 FM100 / AFCI Charge Controller Wiring & Settings
The FM100 and FM100 AFCI charge controllers Aux terminals 7 and 8 must be utilized for the Battery Sense to
function. Refer to page 21 of the FM100 charge controller manual for additional information regarding the
device’s Battery Sense terminals and Battery Sense function:
http://www.outbackpower.com/downloads/documents/charge_controllers/flexmax_100/flexmax100_manual.pdf
A twisted-pair cable can be wired from Aux terminal 7 (negative) and 8 (positive) to any of the (respective)
negative and positive battery terminals in the PHI Battery bank. If the system includes more than one charge
controller, daisy chain the wiring from Aux terminals 7 and 8 in the multiple charge controllers.