Outback Power Integration Guide

REV042920
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com| SimpliPhiPower.com
| 21 |
Table 6.0 Battery Voltage VS. State of Charge (SOC) at C/2 Discharge Rate
SOC
51.2V
nom
PHI Battery
25.6V
nom
PHI Battery
12.8V
nom
PHI Battery
100% > 52.5 VDC > 26.25 VDC > 13.13 VDC
95% 51.7 VDC 25.9 VDC 12.93
90% 51.65 VDC 25.8 VDC 12.91
75% 51.4 VDC 25.7 VDC 12.85
50% 51.0 VDC 25.5 VDC 12.75
20% 50.2 VDC 25.1 VDC 12.55
10% 49.5 VDC 24.8 VDC 12.38
0% 48.0 VDC 24.0 VDC 12.0
4.5 MATE3s Settings
4.5.1 FNDC Advanced Control
The MATE3s System Display and Controller allows for the monitoring and programming of all connected
OutBack equipment.
Table 7.0 Settings for SimpliPhi PHI Battery w/ OutBack FLEXnet DC Advanced Control
FNDC Advanced Control
FNDC Advanced Control Low SoC Warning = 20%
FNDC Advanced Control Critical SoC Warning = 10%
4.5.2 Advanced Generator Start
Advanced Generator Start (AGS) capabilities are built into OutBack equipment. Refer to OutBack’s GS
Load Center Manual for generator wiring instructions, and program the AGS via the MATE3s. According
to OutBack, “AGS Mode utilizes the auxiliary (AUX) output on the inverter or charge controller and is
compatible with any
two-wire start generator.” Verify generator compatibility directly with OutBack
Power:
Support@OutBackPower.com. Refer to page 117 in the MATE3s manual for the AGS Functional
Test.
In the MATE3s’s Main Menu (accessed by pressing the TOP key on the MATE3s), select Settings, then
MATE3s, then Advanced Generator Start.