3.7 Pad Mounting
3.7.1 Pad Requirements
The AccESS must be installed and secured on level concrete. For a pre-cast concrete pad, a 4”
minimum thickness is required. The pad should be 3” wider than the AccESS on all sides (34” x 22
x 4”).
The AccESS is not suited for wall mounting. Any attempt to wall mount the AccESS unit will Void
the Warranty.
3.7.2 Pad Mounting the SimpliPhi AccESS
Six 1-inch knockouts are located in the base of the AccESS for tool accessibility when mounting
the AccESS to the concrete pad. Cover knockout holes with sealing tape after pad mount
installation, and prior to installing the PHI 3.8 Batteries into the base of the cabinet. Not all
knockouts have to be used, depending on the different assets built into the AccESS system to
meet the customer’s needs. Any attempt to wall mount the AccESS unit will Void the Warranty.
Secure the AccESS to the concrete with concrete anchors, such as threaded rods, masonry bolts,
or carriage bolts, minimum ½” diameter. Existing concrete floors in the garage or other areas are
adequate “mounting pads” if the thickness meets the 4” minimum thickness. See Figure 5.0 below
for details.