Figure 14.0 Inverter AC Load Display
Confirming Battery Charger Operation
7. Apply AC from grid or generator. LEDs will blink while the power source is qualified.
8. Check LEDs (AC1 or AC2) on the front panel. One of them must be ON for the unit to
charge.
9. Check the amp (A) LED. If the A LED is ON, the unit is charging and the PHI 3.8 Battery
current is displayed on the inverter information panel.
Figure 15.0 Inverter Charge Rate Display
This completes the functional test. The internal set points have been pre-programmed for the PHI
3.8 Battery bank.
4.6 AccESS Optional Components/Accessories Installation
4.6.1 DC Coupled PV 4.8 kW
The AccESS may be DC Coupled with a PV system up to 4.8 kW DC. Please refer to Schneider
Electric’s MPPT 80 600 installation manual and wiring diagrams for further information.
4.6.2 Remote System Monitoring
Schneider Electric Conext ComBox