AccESS Installation Manual
Table Of Contents
REV020620
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com| SimpliPhiPower.com
| 32 |
Table 3.0 – Programming Settings for SimpliPhi PHI 3.8 kWh 48V Battery w/Schneider Electric Inverter XW Pro or XW+ 6848
INVERTER – XW Pro or XW+ 6848
10K Cycles Warranty
5K Cycles Warranty
3.5K Cycles Warranty
Advanced Settings > Inverter Settings
80% DoD
90% DoD
100% DoD
Low Battery Cut-Out Voltage
1
48V
(50.5V Recommended)
48V
(49.8V Recommended)
48V
LBCO Hysteresis
2.0V
LBCO Delay
10 Sec
High Batt Cut Out
60V
Search Watts
Default
Search Delay
Default
Charger Settings > Custom Settings
Batt Type
Lithium Ion
Lithium Ion
Control
2StgNoFloat
Bulk Voltage
54.4V
54.4V
56V
MaxBulkCurrent (C/2)
2
37.5A per PHI3.8; (112.5A for 3, 150A for 4)
DisChgImax
2
60A per PHI3.8; (180A for 3, 240A for 4)
To calculate as a percentage, divide the relevant Amp value by 140A (128% for 3,
171% for 4)
DisChgImax Timer
s
Batt Capacity
2
75Ah per PHI3.8; (225Ah for 3, 300Ah for 4)
Max Charge Rate (C/2)
2
37.5A per PHI3.8; (112.5A for 3, 150A for 4)
To calculate as a percentage, divide the relevant Amp value by 140A (
80%
for 3,
100% for 4 or more)
Default Batt Temp
Warm
Recharge Volts
50.6V
Absorb Time
120 Minutes
Notes:
1. Maximum setting of 48V limited by some inverter firmware is below the recommended setting.
2. Per PHI 3.8 Battery – These setting are calculated by multiplying the nominal per battery value times the # of batteries.
3. Levels are typical @ 25C and may need adjusting at temperature extremes.
4. When performing rapid deep charge/discharge cycles the battery should be allowed to "rest" 15 minutes in between.
Note: Instead of the Lithium Ion sub-menu, the Custom battery menu may be used instead.
In this case, use the following settings: