Table 3.0 Programming Settings for SimpliPhi PHI 3.8 kWh 48V Battery w/Schneider Electric Inverter XW Pro or XW+ 6848
INVERTER XW Pro or XW+ 6848
10K Cycles Warranty
5K Cycles Warranty
3.5K Cycles Warranty
Advanced Settings > Inverter Settings
80% DoD
90% DoD
100% DoD
Low Battery Cut-Out Voltage
1
48V
(50.5V Recommended)
48V
(49.8V Recommended)
48V
LBCO Hysteresis
2.0V
LBCO Delay
10 Sec
High Batt Cut Out
60V
Search Watts
Default
Search Delay
Default
Charger Settings > Custom Settings
Batt Type
Lithium Ion
Lithium Ion
Control
2StgNoFloat
Bulk Voltage
54.4V
54.4V
56V
MaxBulkCurrent (C/2)
2
37.5A per PHI3.8; (112.5A for 3, 150A for 4)
DisChgImax
2
60A per PHI3.8; (180A for 3, 240A for 4)
To calculate as a percentage, divide the relevant Amp value by 140A (128% for 3,
171% for 4)
DisChgImax Timer
s
Batt Capacity
2
75Ah per PHI3.8; (225Ah for 3, 300Ah for 4)
Max Charge Rate (C/2)
2
37.5A per PHI3.8; (112.5A for 3, 150A for 4)
To calculate as a percentage, divide the relevant Amp value by 140A (
80%
for 3,
100% for 4 or more)
Default Batt Temp
Warm
Recharge Volts
50.6V
Absorb Time
120 Minutes
Notes:
1. Maximum setting of 48V limited by some inverter firmware is below the recommended setting.
2. Per PHI 3.8 Battery These setting are calculated by multiplying the nominal per battery value times the # of batteries.
3. Levels are typical @ 25C and may need adjusting at temperature extremes.
4. When performing rapid deep charge/discharge cycles the battery should be allowed to "rest" 15 minutes in between.
Note: Instead of the Lithium Ion sub-menu, the Custom battery menu may be used instead.
In this case, use the following settings: