AccESS Installation Manual
Table Of Contents
REV020620
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com| SimpliPhiPower.com
| 33 |
Table 4.0 – Programming Settings for SimpliPhi PHI 3.8 kWh 48V Battery w/Schneider Electric Inverter XW Pro or XW+ 6848
INVERTER – XW Pro or XW+
6848
10K Cycles Warranty
5K Cycles Warranty
3.5K Cycles
Warranty
Advanced Settings > Inverter Settings
80% DoD
90% DoD
100% DoD
Low Battery Cut-Out Voltage
1
48V
(50.5V Recommended)
48V
(49.8V Recommended)
48V
LBCO Hysteresis
2.0V
LBCO Delay
10 Sec
High Batt Cut Out
60V
Charger Settings > Custom Settings
Batt Type
Custom
Custom
Eqlz Support
Disabled
Bulk Voltage
54.4V
54.4V
56V
Absorb Voltage
54.4V
54.4V
56V
Float Voltage
N/A (disabled); 54V may be used as a placeholder value
Batt Temp Comp
0 mv/C
Batt Capacity
2
75Ah per PHI3.8; (225Ah for 3, 300Ah for 4)
Max Charge Rate (C/2)
2
37.5A per PHI3.8; (112.5A for 3, 150A for 4)
To calculate as a percentage, divide the relevant Amp value by 140A (
80%
for 3,
100%
for 4 or more)
Charge Cycle
2-Stage
Default Batt Temp
Warm
Recharge Volts
50.6V
Absorb Time
120 Minutes
Note: Consider Charge Block Start and Charge Block Start in the inverter’s Advanced Settings > Charger
Settings menu. If this system includes a grid connection to a utility with higher electricity rates during
certain peak times, it is recommended to set the Charge Block window during peak utility rate hours. If the
batteries reach their
ReCharge Volts setting during the Charge Block window, the batteries will not
recharge from the grid until the end of the Charge Block time period; the batteries are still able to charge
from a connected charge controller or generator during this window.