AccESS Installation Manual
Table Of Contents
REV020620
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com| SimpliPhiPower.com
| 34 |
Inverter Programming Settings for an AC Coupled System
In an AC Coupled system, the only recommended system setup is a Grid-Tie with Battery Backup
application. During normal system operation, this setup allows for the coupled grid-tie inverter(s) to power
the home’s loads and sell excess energy to the grid, while the batteries typically remain fully charged. In the
event of a grid failure while the sun is shining, the coupled grid-tie inverter(s) continue to produce power,
and local loads* are powered with solar PV and/or batteries. In the event of a grid failure while no solar
power is available, the batteries discharge to power local loads*.
*Local loads are those circuits on the inverter’s AC distribution panel; circuits that are located on the home’s main
house panel are not considered local loads.
In an AC Coupled system operating normally, power from the coupled grid-tie inverter(s) passes through
the Conext Mini PDP to the grid. Therefore, the Conext XW Pro or XW+ inverter’s
Sell parameters are not
used and
Sell remains as its default value of [Disabled].
In addition to the pre-programmed settings outlined in Table 3.0, ensure that the following parameters are
set in an AC Coupled / Grid-Tie with Battery Backup system:
INVERTER – XW Pro or XW+
Setup
Grid Support
Disabled
Advanced Settings > Grid Support
Sell
Disabled
Load Shave
Disabled
Advanced Settings > Adv Features
AC Coupling
Enabled
5.3.2 – MPPT Programming Settings
Table 4.0 – Programming Settings for SimpliPhi PHI 3.8 kWh 48V Battery w/Schneider Electric Conext MPPT 80 600
XW MPPT80
10K Cycles Warranty
5K Cycles Warranty
3.5K Cycles Warranty
Advanced Settings > Charger Settings
80% DoD
90% DoD
100% DoD
Batt Type
Custom
Custom Settings
Eqlz Supt
Disabled
Bulk Voltage
54.4V
54.4V
56V
Absorb Voltage
54.4V
54.4V
56V
Float Voltage
54V
Batt Temp Comp
0mV/C
Batt Capacity
2
75Ah per PHI3.8; (225Ah for 3, 300Ah for 4)
Max Charge Rate (C/2)
2
37.5A per PHI3.8; (100% 80A for 3 or more)
Charge Cycle
3 Stage
ReCharge Volts
50.6V
Absorb Time
120 Minutes
Default Batt Temp
Warm
Batt Voltage (Auto-detected)
48V
Aux Settings
Not Used
…
Default
Inverter Programming Settings for a DC Coupled System
DC Coupled Scenario A: Maximize Renewable Energy Self-Consumption
Enable Grid Support to discharge the batteries to a programmed value before the connected grid is
introduced to the renewable energy system to assist with supporting local loads.