Function
120 V/240 V
120 V
Response Time
Anti
-islanding reconnect
254.4 V (± 3 V)
127.2 V (± 3 V)
300 s (+1/
0 s)
Over frequency disconnect
60.5 Hz (± 0.05 Hz)
60.5 Hz (± 0.05 Hz)
60 ms (± 20 ms)
Under frequency disconnect
59.3 Hz (± 0.05 Hz)
59.3 V (± 0.05 Hz)
60 ms (± 20 ms)
Over voltage LN fast disconnect
135 V (± 1.5 V)
135 V (± 1.5 V)
60 ms (± 25 ms)
Over
voltage LN slow disconnect
132 V (± 1.5 V)
132 V (± 1.5 V)
500 ms (± 50 ms)
Over voltage L1/L2 fast disconnect
270 V (± 3 V)
60 ms (± 25 ms)
Over voltage L1/L2 slow disconnect
264 V (± 3 V)
500 ms (± 50 ms)
Under voltage LN fast disconnect
67 V (±
5 V)
75 V (± 5 V)
60 ms (± 25 ms)
Under voltage LN slow disconnect
105.6 V (± 1.5 V)
105.6 V (± 1.5 V)
1000 ms (± 40 ms)
Under voltage L1/L2 slow disconnect
211.2 V (± 3 V)
100 ms (± 40 ms)
Under voltage L1/L2 fast disconnect
150 V (± 10 V)
60 ms
(± 25 ms)
A.3 Schneider Electric Conext XW+ Series Inverter/Charger Overload
Capability
Loads connected to the inverter are seldom constant, and large loads are often operated for short periods.
To accommodate larger loads, the Conext XW+ can temporarily exceed its continuous output power rating.
The graphs below illustrate approximate operation time versus load. Inverter operation time during
overload is limited by both inverter internal temperature protection and by the product of AC output
current and elapsed time.
Figure 16.0 Conext WX+ Operating Time vs 240VAC Load Graph