Service manual
62
1�3 Error description
If some error occurs when the unit is running, the error code will be displayed on the wired controller and the main 
board   of the outdoor unit.See the table before for more details about the meaning of each error.
Residential AC Errors Commerical AC Errors
Outdoor Unit 
"88" Display
Indicating Lamp
Lamp Panel 
"88" Display 
(Floor Ceiling 
Type)
Wired 
Controller 
Display
Running  Cooling  Heating
/ Defrosting mode 1 08 / / / / /
/ Defrosting mode 2 0A / / / / /
/ heating overload protection 0C
Flash 3 
times
Flash 3 
times
Flash 3 
times
/ oE
/ Normal running ON / / / / /
Short/open circuit 
of the liquid valve 
temperature sensor
Short/open circuit of he liquid 
valve temperature sensor
Shown as 
Table 16
/
Flash 19 
times
/ b5 b5
Short/open circuit of the gas 
valve temperature sensor
Short/open circuit of the gas 
valve temperature sensor
Shown as 
Table 16
/
Flash 22 
times
/ b7 b7
Refrigerant insufciency 
or blockage protection 
(available for the 
residential outdoor unit)
Refrigerant insufciency or 
blockage protection (available 
for the residential outdoor unit)
F0 /
Flash 10 
times
/ oE oE
Short/open circuit of 
the indoor ambient 
temperature sensor
Short/open circuit of the indoor 
ambient temperature sensor
Shown as 
Table 16
/
Flash 
once
/ F1 F1
Short/open circuit of 
the indoor evaporator
Short/open circuit of the 
indoor evaporator
Shown as 
Table 16
/
Flash 
twice
/ F2 F2
Short/open circuit of the 
of the outdoor ambient 
temperature sensor
Short/open circuit of the 
of the outdoor ambient 
temperature sensor
F3 /
Flash 3 
times
/ F3 F3
Short/open circuit of 
the temperature sensor 
at the midway of the 
condenser coil ( for the 
commercial unit)
Short/open circuit of the 
temperature sensor at the 
midway of the condenser coil 
( for the commercial unit)
F4 /
Flash 4 
times
/ F4 F4
Short/open circuit of 
the outdoor discharge 
temperature sensor
Short/open circuit of 
the outdoor discharge 
temperature sensor
F5 /
Flash 5 
times
/ F5 F5
Oil returning in cooling
Oil returning in cooling F7 / / / / /
System high pressure 
protection
System high pressure 
protection
E1
Flash 
once
/ / E1 E1
Anti-freezing protection Anti-freezing protection E2
Flash 
twice
/ / E2 E2
System low pressure 
protection (reserved)
System low pressure protection E3
Flash 3 
times
/ / E3 E3
Compressor discharge high 
temperature protection
Compressor discharge high 
temperature protection
E4
Flash 4 
times
/ / E4 E4
Whole unit over-
current protection
Whole unit over-
current protection
E5
Flash 3 
times
Flash 3 
times
Flash 3 
times
oE oE
Communication error 
between the indoor 
and outdoor units
Communication error between 
the indoor and outdoor units
Shown as 
Table 16
Flash 6 
times
/ / E6 E6
Mode conict Mode conict
Shown as 
Table 16
Flash 7 
times
/ / E7 E7
Overload protection Overload protection E8
Flash 3 
times
Flash 3 
times
Flash 3 
times
oE oE
Anti cold blow protection /
E9
/ / / / /
/
Indoor unit water 
overow error
/ Flash Flash E9 E9
Trial run/trial operation Trial run/trial operation dd
Quick 
ash
Quick 
ash
Quick 
ash
dd dd
Refrigerant recovery mode Refrigerant recovery mode Fo
Quick 
ash
Quick 
ash
/ Fo Fo
Drive module resetting
(
for 
the commercial unit)
IPM Drive module resetting P0
Flash 3 
times
Flash 3 
times
Flash 3 
times
oE oE
60