INTEGRATION WITH SKF @PTITUDE OBSERVER
Hierarchy view adding sensors and measurements
24 (84)
SKF Enlight Collect IMx-1 System
User Manual
Revision A
The four measurements each have their own sub-tab in the sensor configuration
dialog:
Sub-tabs for each measurement type typically have three zones where aspects of
that measurement can be configured or are available for review:
General: an area to report the measurement name, engineering units and
scaling.
Acquisition: for the vibration measurements, an area to configure the
number of lines and to view the measurement configuration. By default the
“No. of lines” is set to the maximum value allowed.
Alarms: for all measurements an area to configure, set or disable alarms
associated with each. Note that low warning and low alarm are available only
for temperature measurements. All alarms are disabled by default, with
thresholds set to zero.