MAINTENANCE FUNCTIONS
SKF Enlight Collect gateway
SKF Enlight Collect IMx-1 System
User Manual
Revision A
53 (84)
Bluetooth, the user chooses from a list of gateways that are in range
The user can at this point, select ‘decommission’.
App shows confirmation of successful decommissioning or error
Decommissioning sets the gateway back to a factory default state:
disables the network and mesh radio interfaces
erases configuration, measurement and event data stored on the gateway
and the sensor firmware package
Notes:
The current gateway firmware is maintained, not reverted.
The steps taken above in @ptitude Observer and on site using the app are
independent and any one action can be taken without the other with no significant
consequences. Any one action will stop the measurement data flow from that
machine, or machines, to @ptitude Observer. Until the Hardware ID is cleared
another gateway cannot replace the earlier unit and until it is replaced or the ID
cleared, some errors may be logged due to the loss of connection with the
decommissioned gateway.
Also note that measurement data already transferred to @ptitude Observer remains
available.
To decommission a gateway follow the guidance above, using the Delete button to
remove a gateway is different and should not be actioned without recognising that it
has the following implications:
Associated relay sensors will be deleted.
Gateways cannot be deleted without first unlinking them from associated
machines.
Unlinking a gateway from a machine requires any commissioned sensors to
be deleted first, thereby losing any associated measurement data.
4.2.4 Replacement
Gateway replacement maybe required if a faulty or damaged gateway is identified. A
specific feature/function for gateway replacement is not included in this release,
replacement is achieved by decommissioning the old gateway and then
commissioning the new gateway.
4.2.5 Gateway maintenance
The SKF Enlight Collect Gateway hardware is designed to be maintenance free and
incorporates no batteries and no fans.
It does not contain any user accessible fuses. Active power limitation is used with an
internal fuse acting only as a last resort protection in case of failure of this circuitry.
Any repairs can only be carried by an SKF repair centre.