Figure 27 Example of connector/cable assemblies
Longer cable assemblies or intermediate junction boxes may be required depending
on site layout and requirements.
3.2.2 Power requirements
The SKF Enlight Collect Gateway is designed to be powered from either PoE or an
industrial range 24 V DC supply, including 12 V battery operation. The connection
details for the DC supply are as shown in the figure and table below.
Figure 28 Incoming power supply connection
Table 1 DC in connections
DC Power In
Connector pin
Cable core colour
0 V (Power supply return)
1 and 4
Blue/White
+ 24 V (936V DC)
2 and 3
Brown/Black
Refer to the Important safety warnings.
It is recommended to use all 4 connections to minimise voltage drop across the
cable.
Incoming power is isolated from other gateway circuitry.