Access the Event log from On-line > Event Log.
For an Enlight Collect IMx-1 System, class will be shown as ‘S’.
Event types cover a range of different conditions related to firmware update,
configuration change, loss of connectivity, gateway restart or reset, user log-
in to the gateway and integrity checks, etc.
The display can be filtered by the DAD that is the source of the event, for
example a specific gateway, by date range and by event Type:
Figure 34 Event log filtering
Count is related to the duration of an event:
o 0 for an event without duration, for example gateway restarted.
o 1 event ‘start’ for example log-in or loss of connectivity.
o -1 for event ‘end’ for example log-out or connectivity regained.
Some event types are ‘adapted’ for a wireless sensor:
o A gateway detecting that a sensor has not responded to a
communication, 3 tries at 5-minute intervals, results in a ‘Sensor
temporarily unavailable event. This causes @ptitude Observer to set
a, sensor ‘Not measured’, status.
o A gateway detecting that a sensor has been unavailable for 24-hours
results in a ‘Sensor not available’ event that causes @ptitude
Observer to set a sensor ‘Cable fault’ status.
o Note also that in terms of the status displayed in the @ptitude
Observer hierarchy, receiving no measurement data for twice the
expected interval will also cause the sensor and its measurement
points to be set to ‘Not measured’ status.
An Export function allows the export of events to an Excel file for further
analysis or sharing.