User's Manual

Parking Column 1
Parking Column for System SPT 400 1.2
© SKIDATA AG, Version 1.0 Page 9
Ensure the following before proceeding with electrical con-
nections:
Check for proper mains supply voltage (120 V or 230 VAC)
Mains connections must comply with national standards and
guidelines
When using flexible stranded wires, all filaments must be
placed inside the terminal clamps (use wire-end sleeves, if
necessary)
The mains supply line must be fused in accordance with ap-
plicable regulations (6 A fuse recommended)
Check the isolation resistance of the cables to make sure it
exceeds 0.5 M
Fix cables to mounting plate by way of tension relieve tongues
and cable ties
Check the network cables to ensure the proper loop imped-
ance
Important: Always make sure that the device is completely
disconnected from the mains while fitting electric wiring.
1.2.3 Stripping connection wires
To avoid danger of short circuit with wires or chassis parts, wires
should not be stripped by more than 6 mm (recommended
value). Uninsulated wire sections must be inserted completely
into the connection terminals.
When attaching connecting wires, the insulation should cover the
wire up to the point where it connects to the terminal.
Fig. 5:
Correct connector wiring