Specification

4
1
2
1
13
16
3
3
16
1
17
32
1
1
2
1
7
7
8
7
8
1
3
8
2
11
16
ORDERING DATA
No. 30-75 COMPLETE BASEBOARD
PACKAGE
Contains heating element and
enclosure. Following items included:
expansion cradles, support brackets,
damper vane, 2" wide splice plate
with 5' lengths and longer.
LENGTHS: 2', 3', 3
1
/2', 4', 5', 6', 7', 8',
10', 12'
No. 30-DW ENCLOSURE ONLY
PACKAGE
(All parts and lengths as
No. 30-75 WITHOUT heating element
or expansion cradles.)
N0. E-75
3
/4" ELEMENT ONLY
PACKAGE
Heating element with expansion
cradles; NO enclosure.
LENGTHS: 2', 3', 3
1
/2', 4', 5', 6', 7', 8'
PACKAGING
Each baseboard or enclosure only unit
is individually packed—completely
assembled—in its own Zip-strip carton,
with end flaps clearly marked and
color-coded. See R-01 price list for
packaging of accessories.
HEATING ELEMENT SPECIFICATIONS
:
Furnish and install E-75 baseboard
heating element as manufactured by Slant/Fin
Corporation, consisting of
3
4" nominal copper
tubing, with 2
5
8" x 2
1
8" x .009" aluminum fins,
bent to 2
5
16" x 2
1
8", spaced 55 per linear foot. A
flange with four teeth shall be formed on each
fin to increase thermal contact and to space and
lock the fins uniformly in place. One end of each
element tube shall be expanded to receive the
unexpanded end of another, without couplings.
© Slant/Fin Corp. 2017 • Printed in U.S.A. 417 • Publication No. 30-10
HOT WATER RATINGS
Fine/Line 30 – No. 30-75 baseboard with 3/4" E-75 element.
BTU/hr./ft. with 65˚ entering air
† Millinches per foot. *Ratings at 140˚F and lower temperatures determined by multiplying 150˚F
rating by the applicable factor specified in testing and rating standard for baseboard radiation.
NOTE: Ratings are for element installed as per drawing shown here, with damper open, with expansion cradles. Ratings are based
on active finned length (5" to 6" less than overall length) and include 15% heating effect factor. Use 4 gpm ratings only when flow
is known to be equal to or greater than 4 gpm; otherwise 1 gpm ratings must be used.
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600
FAX: (516) 484-5921 Canada: Slant/Fin LT D/ LTEE , Mississauga, Ontario
www.slantfin.com
BRACKETS PER LENGTH
COVER ASSEMBLY SPECIFICATIONS: Furnish and install Fine/Line 30-75
baseboard cover assembly as manufactured by Slant/Fin Corp. The cover consists of a one-piece
bottom, back and top panel, one-piece front panel and one piece damper vane that are formed
out of galvanized cold rolled steel. Cold rolled steel that is not galvanized is not acceptable. The
galvanized steel makes the cover rust resistant. Bottom and top of back panel shall have channels
along entire length to receive full-height support brackets. Brackets shall add support to the top of
the rear panel. The factory installed damper vane shall modulate fully and freely, while retaining
any setting through its arc. Damper shall swing in position on damper
pivots inserted in die-formed slots towards top of support bracket. Roll formed pivot point is not
acceptable. All cover components shall be painted in a Nu-White, thermosetting polyester enamel.
Brackets shall be die-formed of re-phosphorized cold rolled steel, for rigid bracing and spring
locking. Each length of baseboard shall have a minimum quantity of factory installed brackets per
length of baseboard cover as follows: 2, 3 and 3
1
2' have 2 brackets; 4 and 5' have 3 brackets; 6, 7
and 8' have 4 brackets; 10' has 6 brackets; 12 and 14' have 8 brackets. Fewer brackets are not
acceptable.
Slide-action polypropylene expansion cradles shall protect element bottom and sides from con-
tact with support brackets and cover, allowing free lateral element expansion for noiseless opera-
tion. Cradles shall be installed on heating elements at location of brackets.
END CAP Left end cap
3
3
4"
wide, No. 30-LEC
with piano-hinged Right end cap
front panel, closed No. 30-REC
end. For use at
doorways.
SLOTTED END CAP Left wall trim
3
3
4" wide, No. 30-LEC-SLOT
with piano-hinged Right wall trim
front panel, slotted No. 30-REC-SLOT
end. For use at wall
partitions.
INSIDE CORNER 90˚ inside corner
3
3
4" wide No. 30-IC-90
at top, with piano- 135˚ inside corner
hinged, contoured No. 30-IC-135
front panel. 91˚to 179˚field
adaptable inside
corner No. IC-FA
VALVE COVER Left valve cover
8" wide, No. 30-LVC
with extra wide No. 30-RVC-SLOT
piano-hinged front Right valve cover
panel, closed end. No. 30-RVC
(30-CVC has open ends.) No. 30-RVC-SLOT
Center valve cover
No. 30-CVC
FILLER SLEEVE (3 piece set)
Cover gaps from 7" filler sleeve
1" to 6" or No. 30-FS-7
1" to 12"
Includes back, 14" filler s
sleeve
top and front panels No. 30-FS-14
and damper vane.
OUTSIDE
90˚outside corner
CORNER No. 30-OC-90
One-piece unit without 135˚ outside corner
hinged panels. No. 30-OC-135
SOLID
WALL TRIM
/SPLICE PLATE 2" solid
2" or 4" solid No. 30-WT-2
(non-hinged), with open
ends. For use at left or 4" solid
right wall partitions or wall t
trim
as one- piece filler sleeve. No. 30-WT-4
(OPTIONAL)
SPLICE PLATE
Note: 3 pc splice plate
available to order
Touch-Up Paint
4.5 oz touch up paint
- spray can
Fine/Line 30 Hinged Accessories
WATER
FLOW
PRESSURE
DROP
110˚F 120˚F 130˚F 140˚F 150˚F 160˚F 170˚F 180˚F 190˚F 200˚F 210˚F 215˚F 220˚F
1 GPM 47 160* 210* 260* 320* 380 450 510 580 640 710 770 810 840
4 GPM 525 160* 220* 270* 340* 400 480 540 610 680 750 810 860 890
Length, ft. 2 - 3.5 4 - 5 6 - 8 10 12 - 14
Brackets 2 3 4 6 8

Summary of content (1 pages)