Length, ft. 2 - 3
1
2 4 - 5 6 - 8 10 12 - 14
Brackets 23468
ORDERING DATA
No. 30-75 COMPLETE BASEBOARD
PACKAGE
Contains heating element and
enclosure. Following items included:
expansion cradles, support brackets,
damper vane, 2" wide splice plate
with 5' lengths and longer.
LENGTHS: 2', 3', 3
1
/2', 4', 5', 6', 7', 8',
10', 12'
No. 30-DW ENCLOSURE ONLY
PACKAGE
(All parts and lengths as
No. 30-75 WITHOUT heating element
or expansion cradles.)
N0. E-75
3
/4" ELEMENT ONLY
PACKAGE
Heating element with expansion
cradles; NO enclosure.
LENGTHS: 2', 3', 3
1
/2', 4', 5', 6', 7', 8'
PACKAGING
Each baseboard or enclosure only unit
is individually packed—completely
assembled—in its own Zip-strip carton,
with end flaps clearly marked and
color-coded. See R-01 price list for
packaging of accessories.
HEATING ELEMENT SPECIFICATIONS
:
F
urnish and install E-75 baseboard
heating element as manufactured by
Slant/Fin Corporation, consisting of
3
4"
nominal copper tubing, with 2
5
8" x 2
1
8" x
.009" aluminum fins, bent to 2
5
1
6
" x 2
1
8",
spaced 55 per linear foot. A flange with
four teeth shall be formed on each fin to
increase thermal contact and to space and
lock the fins uniformly in place. One end of
each element tube shall be expanded to
receive the unexpanded end of another,
without couplings.
© Slant/Fin Corp. 2010. Printed in U.S.A.110. Publication No. 30-10
Fine/Line 30 Hot water baseboard radiation
Multi/Pak 80 for high output
Use high capacity Multi/Pak 80 baseboard
in locations where wall space is limited and
higher output is required. Frequently specified for
commercial, industrial and apartment use,
Multi/Pak 80 is compact, rugged and easy to
install and features interchangeable heating
elements. Ratings with the
3
4" elements most
commonly selected for residential use are 1030
Btuh (H-1 element) and 940 Btuh (H-3 element).
For more information, see Pub. 80-10
Hydronic Floor Box Heater
The Hydronic Floor Box provides
uninterrupted heating comfort at glass wall areas
such as patio doors and floor length windows. It
recesses neatly into the floor to become part of
your baseboard loop. A hefty steel grille overlaps
floor opening and is easily removed for cleaning.
Using a 5 foot H-3 heating element, the unit
provides 4040 Btuh at 200°F water temp.,
4 g.p.m. flow.
For more information, see Pub. HFB-10.
Dimensions: Enclosure 62
9
16" x 6
3
16" x 8
9
16" high;
Grille: 65" x 8"
The Kicker
This multi-purpose fan convection heater is ideal
for use in kitchens, bathrooms and other areas
where there’s not enough wall space for base-
board. It provides enough heat output to equal
up to 12 feet of baseboard. Fits in kickspace
under cabinets or vanities. Recessed or surface
wall mount kits also available. Connects to boiler
in series with baseboard or as a separate zone.
For more information, see Pub. TK-10
WATER PRESSURE
1
40˚F 150˚F 160˚F 170˚F 180˚F 190˚F 200˚F 210˚F 215˚F 220˚F
FLOW DROP†
1
GPM 47 320* 380 450 510 580 640 710 770 810 840
4 GPM 525 340* 400 480 540 610 680 750 810 860 890
OTHER SLANT/FIN PRODUCTS TO MEET YOUR HEATING NEEDS.
I=B=R APPROVED HOT WATER RATINGS
F
ine/Line 30 No. 30-75 baseboard with 3/4" E-75 element.
B
TU/hr./ft. with 65˚ entering air
Millinches per foot.
*
Ratings at 140˚F and lower temperatures determined by multiplying 150˚F
rating by the applicable factor specified in Table E in the I=B=R Testing and Rating Standard for Baseboard radiation.
NOTE: Ratings are for element installed as per drawing shown here, with damper open, with expansion cradles. Ratings are based
on active finned length (5" to 6" less than overall length) and include 15% heating effect factor. Use 4 gpm ratings only when flow
i
s known to be equal to or greater than 4 gpm; otherwise 1 gpm ratings must be used.
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600
FAX: (516) 484-5921 Canada: Slant/Fin LTD/LTEE, Mississauga, Ontario
www.slantfin.com
BRACKETS PER LENGTH
Complete assembly and enclosure only
C
OVER ASSEMBLY SPECIFICATIONS:
F
urnish and install Fine/Line 30-75
baseboard cover assembly as manufactured by Slant/Fin Corp. The cover consists of
a one-piece bottom, back and top panel, one-piece front panel and one piece damper
v
ane that are formed out of galvanized cold rolled steel. Cold rolled steel that is not
galvanized is not acceptable. The galvanized steel makes the cover rust resistant.
Bottom and top of back panel shall have channels along entire length to receive
f
ull-height support brackets. Brackets shall add support to the top of the rear panel.
The factory installed damper vane shall modulate fully and freely, while retaining any
setting through its arc. Damper shall swing in position on damper pivots inserted in
die-formed slots towards top of support bracket. Roll formed pivot point is not
a
cceptable. All cover components shall be painted in a Nu-White, thermosetting
p
olyester enamel.
Brackets shall be die-formed of re-phosphorized cold rolled steel, for rigid bracing
and spring locking. Each length of baseboard shall have a minimum quantity of factory
installed brackets per length of baseboard cover as follows: 2, 3 and 3
1
2' have 2 brack-
ets; 4 and 5' have 3 brackets; 6, 7 and 8' have 4 brackets; 10' has 6 brackets; 12 and
14' have 8 brackets. Fewer brackets are not acceptable.
Slide-action polypropylene expansion cradles shall protect element bottom and sides
from contact with support brackets and cover, allowing free lateral element expansion
for noiseless operation. Cradles shall be installed on heating elements at location of
brackets.