Install Instructions

INTREPID
23
BURNER DATA – CARLIN EZ-1HP PRO & EZ-2HP PRO FOR PACKAGED BOILERS ONLY
BOILER
MODEL
BURNER
MODEL
FIRING 
RATE
NO.2 OIL
(GPH)
NOZZLE
OIL PUMP
PRESSURE
SETTING
(PSIG)
APPROX.
AIR BAND
SETTING
NO.
HEAD
POSITION 
BAR USED
(GPH)
SIZE
(GPH)
ANGLE &
TYPE MFR.
TR-20 EZ-1 HP 0.75 0.65 70˚W DELAVAN 140 0.75 0.50
TR-30 EZ-1 HP 1.10 0.85 70˚A DELAVAN 165 0.90 0.75
TR-40H EZ-2 HP 1.50 1.20 60˚B DELAVAN 156 20 #3
TR-40 EZ-2 HP
1.60
1.80
1.20
1.35
60˚B
60˚B
DELAVAN
DELAVAN
178
178
40
40
#3
#4
Note:
1. TR-20 & TR-30 must use a blanket.
2. Only the electrodes and the air band can be adjusted. The burner is supplied with a calibrated bar that properly
position the head in the air tube. See the table above for the head positioning bars used.
3. The air shutters on the burners for models TR-20 & TR-30 are blank (closed).
4. Tripled slotted air shutter on the the burner for model TR-40
SEE TABLE FOR APPROXIMATE SETTINGS
Electrode placement, retention ring assembly and nozzle adapter.