Installation & Operating Manual

FRONT
LEFT SIDE
RIGHT SIDE
7
4 1/2
D
C
2 1/4
4 1/4
B
A
14
1 3/4
E
4
GAS
SHUTOFF
VALVE
PRESSURE
RELIEF
VALVE
Bobcat Models B-120A and B-200A
2
RATINGS AND DIMENSIONS
Figure 1. Dimensions data
Bobcat Boiler
SPECIFICATIONS:
B-120A Boiler B-200A Boiler
Fuel Rate Input:
120,000 BTUH max
30,000 BTUH min
200,000 BTUH max
50,000 BTUH min
Boiler Water Volume:
1.0 gallon (8.3 lbs) 1.4 gallon (11.07 lbs)
Water Piping
Connections:
1 NPT (male)
Weight of Boiler
(uncrated):
145 lbs. 200 lbs.
Gas orifice size:
Natural Gas - No orifice used*
Propane - .2025 inside
diameter
Propane - .2600 inside
diameter
Gas Piping Connection:
1/2 NPT (female)
Vent Connection:
3 nominal I.D. pipe (PVC, CPVC or stainless steel)
Air Intake Connection:
3 nominal I.D. pipe (PVC, CPVC or stainless steel)
*Note: No orifice changes are required for high altitude installations.
Dimension B-120A B-200A
A 22 30
B 23 7/8 31 7/8
C 33 38
D 35 40
E 7 10