Installation & Operating Manual

Bobcat Models B-120A and B-200A
33
MODE DISPLAY
DESCRIPTION
Changing space heating post pump time. Settable from 10 to 900 seconds.
(steps of 10 seconds). The default value is 30 seconds.
Changing DHW post pump time. Settable from 1 to 255 seconds.
(steps of 1 seconds). The default value is 15 seconds.
Changing space heating control mode
0: Thermostat only (default) - boiler without outdoor sensor
1: Outside sensor and Thermostat
3: Permanent heat demand (boiler circulator always on)
Changing domestic hot water (DHW) mode
0: No DHW
1: Storage tank with sensor
2: Storage tank with thermostat (default value)
3: Plate heat exchanger
Changing DHW or space heating priority mode
0: DHW priority (no time limit)
1: Space heating priority (no time limit)
2: DHW priority for limited time (default)
3: Space heating priority for limited time
Changing priority limited time. Settable from 20 to 80 minutes.
The default value is 30 minutes.
Boiler model selection, value is 0 for model B-120A and 4 for model B-200A
Boiler model confirmation, value is 0 for model B-120A and 4 for model B-200A
Weather compensation supply water reference temperature
(space heating mode 1). Settable from 16˚F to 122˚F (steps of 1 F).
The default value is 86˚F.
Changing compensation slope (space heating mode 1).
Settable from 0.1 to 5.0 (steps of 0.1).
The default value is 1.0.
Not Utilized
Weather compensation set point.
The value is 68˚F.
Display shows blower RPM (mutiply reading by 10 for actual RPM)
Change blower RPM for high input (steps of 30 RPM, limit +/- 480 RPM).
Change blower RPM for low input (steps of 30 RPM, limit +/- 120 RPM).
Display shows flame current in micro amps
System test – Display shows flame current
0: System test off
L: Steady low input (20 minutes)
I: Steady ignition input (20 minutes)
H: Steady high input (20 minutes)
NOTE: *: Alternating **: Steady
VIEWING AND CHANGING SYSTEM SETTING - Table 5
“To change system setting or perform system test”
The menu is accessed by pressing and holding “SELECT” and “ENTER” buttons for 10 seconds. To access different modes,
press “ENTER” button. To change system setting: Press “UP or DOWN” button, then press “ENTER”
WARNING: Only a trained, experienced service technician or installer should use this table.
*
*
*
*
*
*
*
*
*
*
*
**
*
*
**
*
*